Fan control

14
To obtain energy savings it is possible to pulse control the power supply to the fans at the
evaporators. This function is only active during the thermostat's cutout period.
If pulse control is required, set the period "FanCycl m" as well as the percentage of the period
where the fans are ON.
If "Fan On" is set to 100 per cent, the fans will operate continuously during the cutout period.
Common Controller
Fan Pulsing (Cutout Night)
During forced closing (input "ON" is cut out), the fans can be stopped. The forced closing
function also has an influence on the other outputs, where you may choose between the
following positions:
1: Fan output is in pos. ON, rail heat is pulse controlled (if pulse control has been selected),
and the remaining outputs are in rest position.
2: Fan output is in pos. OFF, otherwise as "1".
3: All outputs are in rest position.
In position 3 the alarm thermostat function is inactive , even if you have selected ON.
Common Controller
Output Ctrl. at Forced Closing
Function description RC.8A.R1.02 © Danfoss 10/2001
Fan On % ___
FanCycl. m ___
1 / 2 / 3
Output Ctrl
AKC 114G