Figure 3-7 Diagrammes en escalier - Modèle 6001
L1 L2 L3
18
JUNCTION BOX
TERMINAL STRIP
O
480V 3
SUPPLY
INTEGRATED CONTROL
X1-3
ON/OFF
SWITCH
X1-12
F2
F4
X1-6
X1-1
SYSTEM PUMP
3.15 A
5.0 A
RELAY
X1-2
BOILER PUMP
RELAY
X1-4
DHW PUMP
RELAY
X1-8
CAM SWITCH
SMALL GAS
X10-1
X10-2
VALVE RELAY
CAM SWITCH
LARGE GAS
VALVE RELAY
X10-3
LARGE GAS
X10-6
VALVE RELAY
SMALL GAS
X10-5
VALVE RELAY
X10-4
X1-3
X1-7
X6-1
X1-10
R3
X2-5
X2-5
X6-3
X6-1
X6-10
X11
X2-5
X13-4
USB
INTERFACE
BLOWER
CONTACTOR
1
2
3
BAS (AS APPLICABLE)
X1-1
X1-2
X1-3
SERVICE OUTLET
480V
TRANSFORMER
FLUE DAMPER
FLUE DAMPER
TRANSFORMER
1
2
M
3
24V
TRANSFORMER
R3
P.O.C. VALVE
CAM SWITCH
P.O.C. VALVE
J3-6
LWCO
TEST
J3-3
PROBE
SWITCH
LWCO
J2-1
LWCO RESET
BOARD
J2-2
CAM
SWITCH
PROPANE LIGHT
NATURAL LIGHT
PROPANE LGPS
NATURAL HGPS
CAM
X6-5
INTEGRATED
SWITCH
CONTROL
PROPANE HGPS
X6-15
PROPANE LGPS
POC
X6-13
X6-12
AIR VALVE
X3-3
PRESSURE SWITCH
X3-4
X13-1
X3-1
BLOCKED FLUE
X6-6
X3-2
SWITCH
BLOCKED DRAIN
X5-1
SWITCH
X5-7
X6-11
CAM
SWITCH
X5-2
X6-2
X5-8
X6-14
X5-3
X5-9
"X5"
BLOCK WIRING
IS MODEL
X6-4
X5-4
DEPENDANT
X5-10
X5-5
X5-41
X5-6
X5-12
Manuel supplémentaire pour Dual Fuel
NEUTRAL
TERMINAL STRIP
OPTIONAL ITEMS
480V SUPPLY "N"
BAS
BOARD
1.5A EACH MAX
(AS APPLICABLE)
TERMINAL STRIP
GROUND
SYSTEM PUMP
CONTACTOR
INTEGRATED
CONTROL
BOILER PUMP
X8-20
CONTACTOR
X8-10
X8-10
DHW PUMP
CONTACTOR
X8-1
X7-8
CONTACTOR
X7-7
X8-13
SMALL
X8-14
NATURAL
VALVE
LARGE
NATURAL
X8-12
VALVE
SMALL
NATURAL
LARGE
X8-11
VALVE
NATURAL
VALVE
X8-5
X8-15
FLAME
CN3-4
SENSE 1
X8-6
SPARK
ROD
X8-16
SPARK
GENERATOR
X8-7
FLAME
SENSE 2
X8-17
X8-18
X8-3
INLET SENSOR
X8-8
BLOWER
OUTLET SENSOR (S9)
X8-2
OUTLET SENSOR (S1)
X8-4
4
FLUE SENSOR
X8-9
FLUE SENSOR (S10)
X7-1
PRE-MIX SENSOR 1 (S11)
X7-5
PRE-MIX SENSOR 1 (S13)
X8-19
AIR VALVE POSITION
X6-18
X6-9
X6-17
X6-8
J3-5
J3-2
J3-4
X4
LG CON BRD
CN-4
CN-1
AIR VALVE
M
CN-2
SHIELDED CABLE FROM X4
TO J12 OR J23 AS APPLICABLE
SMALL
CONNECTION BOARD
CN1-4
CN1-5
CN1-6
1
ALARM
CONTACTS
2
CN1-12
3
RUN-TIME
CONTACTS
4
CN1-10
5
TANK
THERMOSTAT
6
CN1-11
7
R
ENABLE
8
W
CN1-9
9
LOUVER
PROVING
10
CN1-8
11
24 VAC LOUVER
RELAY COIL
12
CN1-7
13
AUX
SWITCH 1
14
CN1-1
15
AUX
SWITCH 2
16
HIGH LIMIT
CN1-2
SWITCH
CN1-3
Notes:
1. All wiring must be installed in accordance with: local, state, provincial and national code requirements per either N.E.C.
in USA or C.S.A. in Canada.
2. If any original equipment wire as supplied with the appliance must be replaced, it must be replaced with wire having same
wire gauge (AWG) and rated for a minimum of 105° C. Exceptions: Replacement high voltage spark lead and
must be purchased from the factory. Use of a non-approved spark lead or
which could result in non-repairable damage to the integrated controller or other components.
3. Actual connector block locations may vary from those shown on diagrams. Refer to actual components for proper
connector block locations when using diagrams to troubleshoot unit.
BOX DEPICTS
BOX DEPICTS
DUAL SENSOR
SINGLE HOUSING
LOW VOLTAGE
120 VAC
HIGH VOLTAGE
LARGE
CONNECTION BOARD
CN6-3
CN6-2
CN6-1
17
SHIELD
18
A
BAS
CN3-6
OPTION
19
B
20
SHIELD
CN3-7
21
+
RATE
0-10V
OUT
-
22
CN3-14
23
+
BOILER
0-10V
PUMP OUT
-
24
CN3-13
25
SYSTEM RETURN
SENSOR
26
CN3-12
27
SYSTEM SUPPLY
SENSOR
28
CN3-11
29
TANK
SENSOR
30
CN3-10
31
OUTDOOR
SENSOR
32
CN3-9
+
33
BMS
0-10V
-
IN
34
CN3-8
35
+
SYSTEM
0-10V
PUMP IN
-
36
CN3-1
37
SHIELD
38
A
CASCADE
CN3-2
39
B
SHIELD
40
CN3-3
CN3-4
-T
-T
-T
-T
-T
-T
-T
RP
1
BLOWER
4
LCD
2
DISPLAY
5
WIFI
DONGLE
8
43
USB CABLE
J6
BAS
J7
SW1
CN6-2
J8
J10
CN6-1
J9
J17
OPTIONAL USB/WIFI
CN6-3
J2
J11
J23
J12
EXTENSION CABLE
24V
E
GND
OPTIONAL
ETHERNET CABLE
shielded
cables
shielded
cables can lead to operational problems
LADDER DIAGRAM