Installation
Make sure service has space to install connecting cables and has
easy access the unit.
Vertical mounting required at ambient temperature > 35 °C
(circulation through ventilation holes).
Mounting and wiring
2
3
4a
/
See figures
Preparation
2
1.
Take off cover
2.
Insert cable tie for KNX cable
4a
Standard mounting on standard rail TH 35-7.5
1.
Mount standard rails
2.
Attach web server to standard rails from above
3.
Push down the web server until it locks
4b
Screw on mounting on a level wall
1.
Drill two holes for the screws
2.
Tighten web server and make sure it is flat (warped housings are
not permitted)
Wiring and final mounting
1.
Switch off KNX devices
2.
Connect KNX cable, terminal 2: CE , terminal 3: CE
3.
Tighten cable tie and cut off the remainder
4.
Break out the notch from the cover
8
5.
Replace the cover

Display and operating elements

12
See figure
page 4
LED displays
1 On
(red/green/orange)
Dark
No power
Steady red
Web server starting (operating system)
Flashing red
Web server starting (application)
Steady green/orange
Web server operational, "Energy indicator = Green
leaf or Orange leaf"
Flashing green/orange
Web server is connected to the remote access portal
2 KNX
(green)
Dark
No bus power
Lit
KNX operational
Flashing
Communication on KNX
3 Reserve
Dark
No function
4 Fault
(red)
Displays faults from the web server or the connected KNX devices.
Dark
No fault
Lit
Acknowledged fault
Flashing
Unacknowledged fault
5 Addressing mode (red)
Dark
KNX addressing mode off
Lit
KNX addressing mode on
Siemens Building Technologies
4b 5 6 7 8
page 2, 3
3
max. 3.5 mm
5
6
7
Operating buttons
The following applies when pressing the buttons
Short:
< 2 seconds
Long:
> 6 seconds
6 Remote
Short
Acknowledges fault message
Long
Sends system report to the configured fault e-mail
receivers; see as well "Button combination".
7 Addressing mode
Short
One-time press sets the web server to the KNX
addressing mode. Pressing the button again switching
off the KNX addressing mode.
Long
See "Button combination"
Button combination
and
Short
No function
Long
Reestablishes default state
Note: This resets all configuration data and settings.
The device list, plant diagrams and all unsent
messages are deleted. History data is not deleted.
Commissioning
9 10 11 12 13
See figures
Caution
Web server connects automatically to the remote access portal as
soon as it has internet access via the Ethernet interface.
Commissioning guide C5701 has information on the remote access
portal (www.siemens.com/ozw772-manual).
Disabling the automatic connection to the portal and commissioning
without the portal is described in commissioning guide C5701.
Prerequisites
Web server is mounted, wired, and connected to the Internet via the
9 11
Ethernet interface
The connected Synco devices are commissioned.
The Synco devices have a valid KNX address [1...253] and are
operational.
Bus power supply to the KNX bus is turned on.
The web server / a connected KNX device is the clock time master
on KNX.
Operating voltage for the web server is switched on.
The web server is ready as soon as the On LED is green or orange.
PC/Laptop has the same or other Internet access.
74 319 0664 0 e
G5701xx
page 3, 4, 5
2014-10-01
en 7/8