CLCM1H,6H,6T DIGITAL WALL MODULES – INSTALLATION INSTRUCTIONS
Explanation: The goal of this action is to reset those overrides which
a room user has enacted at the wall module. Thus, in, e.g., hotels
and office buildings, a typical requirement is to remotely reset the
wall module setpoint override to zero, and to remotely reset the wall
module fan speed override to "Auto".
NOTE:
If the wall module has been set to OFF by the room
user, it cannot be reset to auto.
In the case of PANTHER controllers, this reset can be
done by sending 6 Volt (= "unoccupied") to the LED input of
the wall module:
As long as 6V is being sent to the LED input
the wall module will be in "unoccupied"
the local setpoint and/or fan speed setting will be reset
and disabled.
As long as 10V is being sent to the LED input
the wall module will be in "occupied"
the local setpoint and/or fan speed setting will be
enabled.
In the case of SERVAL controllers, this reset can be done
by switching from "occupied" to "unoccupied". This will send a
specially coded SERVAL signal to the LED input of the wall
module.
"Unoccupied" means:
Effective Unoccupied (moon on continuously) or
Override Unoccupied (moon flashing).
"Occupied" means:
Effective Occupied (sun on continuously), or
Override Occupied (sun flashing).
P9
Limit setpoint
-
Limits setpoint to ±0 ... 5 Celsius (if set to °C) or to
±0 ... 9 °F (if set to °F).
Default (if set to °C): P9:5
Default (if set to °F): P9:9
Example (units set to °C): A setting of
set point offset is limited to -3 to +3 °C.
Example (units set to °F): A setting of
set point offset is limited to -8 to +8 °F.
PA Limit for humidity low limit output value
-
Limits the output value to 10 ... 20% relative humidity in
steps of 5%. This affects the output voltage on pin 7, only,
and has no effect upon values appearing in the display.
= 10%,
= not used.
Resetting to Factory Defaults
Pressing the left, middle, and right button simultaneously
while powering the wall module will reset the wall module
settings to the factory defaults values.
When the reset has been completed, the display will show
.
Manufactured for and on behalf of the Environmental & Energy Solutions Division of Honeywell Technologies Sàrl, Rolle, Z.A. La Pièce 16, Switzerland by its Authorized Representative:
CentraLine
Honeywell GmbH
Böblinger Strasse 17
71101 Schönaich, Germany
Phone +49 (0) 7031 637 845
Fax
+49 (0) 7031 637 740
info@centraline.com
www.centraline.com
means that the
means that the
= 15%,
= 20% (default),
Subject to change without notice
MU1Z-0902GE51 R0416C
Preferred DWM Configurations
Depending upon how you configured (using ARENA/COACH)
the SERVAL application software (as either HYD, CHC, or
FCU), the DWM hardwired to it should be configured as
indicated in Table 4.
Table 4. Preferred DWM configurations in dependence
upon configuration of SERVAL application software
configuration of SERVAL application
HYD
P1:3
P2:2
P3:1
P4:1
P5:2
P6:1
P7:50
P8:4
Depending upon the given application software (either HE01,
HT02, or AH03) which you have chosen to download into
your PANTHER, the DWM hardwired to it should be
configured as indicated in Table 5.
Table 5. Preferred DWM configurations in dependence
upon PANTHER application software
PANTHER application
HE01
P1:3
P2:2
P3:1
P4:1
don't care
don't care
P6:1
P7:50
P8:4
How to Check the Software Version
Simultaneously press the left (FAN OVERRIDE) and right
(BYPASS) buttons for approx. 5 sec: An LCD display test will
then be performed, after which the DWM's current software
version (e.g.: 2.11) is shown in the LCD display.
CHC
FCU
P1:3
P1:3
P2:2
P2:2
P3:1
P3:2, P3:3, or P3:4
P4:1
P4:1
P5:2
P5:2
P6:1
P6:1
P7:50
P7:50
P8:4
P8:4
HT02
AH03
P1:3
P1:3
P2:2
P2:2
P3:1
P3:1 or P3:2
P4:1
P4:1
don't care
P6:1
P6:1
P7:50
P7:50
P8:4
P8:4