 Actuate the oil pump by hand as shown in Table 6. Pull the hand lever
evenly as far as possible or press the pushbutton down as far as possible.
One actuation cycle corresponds to one stroke of the pump's piston.
 After actuation, you must reseal the supply tank tightly.
Meter size:
DN 50
DN 80
DN 100
DN 150
DN 200
DN 250
DN 300
DN 400
DN 500
DN 600
Oil type:
Klüber ISOFLEX PDP 38
Table 5 | Maintenance instructions
73024521a
© Elster GmbH | All rights reserved. Subject to modification
Maintenance instructions
Oil quantity
Oil pump with lever
1.6 ml
1.6 ml
6 ml
6 ml
6 ml
11 ml
11 ml
24 ml
24 ml
24 ml
Oil types
Number of strokes:
Pushbutton oil pump
-
-
15
6
6
11
11
24
24
24
Operating temperature range:
-25°C to +70°C
Honeywell
15
15
-
-
-
-
-
-
-
-
25