Occupancy Sensor Setup - Lutron GRAFIK Eye QSGRJ-3P Guide Rapide D'installation

Masquer les pouces Voir aussi pour GRAFIK Eye QSGRJ-3P:
Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

Occupancy Sensor Setup

Associating wireless occupancy sensors and GRAFIK Eye QS Wireless control units
(for wireless enabled units only):
1. Make sure the wireless mode of the GRAFIK Eye QS control unit is
Main menu
"Enabled".
Zone Setup
2. Enter programming mode.
3. Use the Master buttons to highlight "Sensor setup" and press the
Sensor Setup
OK button to accept.
4. Use the Master buttons to highlight "Add wireless sensors" and
press the OK button to accept.
Sensor Setup
5. Press and hold the "Lights Off" button (
Add wireless sensors
occupancy sensor for 6 seconds. The lens will start flashing and the
info screen on the GRAFIK Eye QS Wireless control unit will display
Daylight
the sensor's serial number.
6. Press the OK button on the GRAFIK Eye QS control unit.
A screen will confirm that the sensor has been assigned.
Add wireless sensors
(To disassociate a wireless occupancy sensor from the GRAFIK Eye
QS control unit, Refer to the Radio Powr Savr occupancy sensor
Initiate association
install guide to return the sensor to its "out-of-box" functionality.
of sensors
Doing so will remove its programming from the GRAFIK Eye QS
control unit.)
7. Repeat the above steps for all desired sensors.
Occupancy
8. Exit programming mode.
xxxx-xxxx
Associating wireless occupancy sensors through
QS Sensor Modules (QSM):
Press OK to Save
1. Press and hold the "Program" button on the QSM for 3 seconds
to enter programming mode. There will be 1 audible beep and the
Status LED will begin flashing. The info screen on the GRAFIK Eye
QS control unit will display that the QSM is in programming mode.
2. Press and hold the "Lights Off" button (
Saved
*Assigned*
occupancy sensor for 6 seconds. There will be 3 audible beeps
from the QSM to verify association.
3. Press and hold the "Program" button on the QSM for 3 seconds to
exit programming mode.
Note: The wireless signal has a range of 30 ft (9 m) through
standard construction or 60 ft (18 m) line of sight.
For additional information, see the complete installation and operation guide at www.lutron.com/qs
g
on some sensors) on the
g
on some sensors) on the
GRAFIK Eye QS Control Unit Quick Installation and Operation Guide
OK
Press and hold "Lights Off"
g
or
button to associate/
disassociate
Radio Powr Savr
Occupancy Sensors
"Program" button
QS Sensor Module (QSM)
Master
buttons
OK
button
Timeclock
(back) button
14

Publicité

Table des Matières
loading

Table des Matières