Control Features; Control Logic - LMF Clima HRH Mode D'emploi

Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

Automatic / manual fan speed selection
Changeover floating valve management
Heating floating valve management
Water coil antifreeze management
Modulating electric heater management (PWM)
Filter pressure switch management
Fan management by CO2 sensor
Fan management by 1 pressure sensor
By-pass damper management
Boost function
Alarm management and diagnostic
Post ventilation
Clock program management
Remote display with internal temperature sensor
BMS Modbus protocol RS485
In the following diagrams is explained the summer-winter control logic
Cooling logic (Summer)
Tsp-Treg
+
= 0.5°C
-
0
-
= 1°C
= Cooling valve proportional band
= Free-cooling differential
= Free-cooling Hysteresis
Only ventilation
By-pass (freecooling)
Cooling modulation 1-99%
Cooling 100%
Example cooling mode (summer):
Treg= 27°C
Tsp= 26°C
Te= 20°C
--------------------------------------------
Tsp-Treg= 26-27= -1°C
Tsp-Te= 26-22= +4°C
firmware 0.26
Electronic Control "HRH-HRS" User Manual

1 Control Features:

2 Control logic

= 2°C
+
Tsp-Te
= 2°C
Treg = regulation probe temperature
Tsp = set point temperature
Te = external probe temperature
= 2°C
-
= 2°C
= Heating valve proportional band
= Free-heating differential
= Free-cooling Hysteresis
Only ventilation
By-pass (freeheating)
Heating modulation 1-99%
Heating 100%
Example heating mode (winter):
Treg= 19°C
Tsp= 20°C
Te= 10°C
-------------------------------------------
Tsp-Treg= 20-19= +1°C
Tsp-Te= 20-10= +10°C
Rev.06
Heating logic (Winter)
Tsp-Treg
+
0
= 0.5°C
= 1°C
-
ENG
+
Tsp-Te
EN 4/ 23