Automatic / manual fan speed selection
3 point cooling / changeover floating valve management
3 point heating floating valve management
Cold water / change over pump management
Hot water pump management
Heat exchanger defrost management
Water coil antifreeze management
On-Off electric heater management
Filter pressure switch management
Fan management by CO
Fan management by 1 or 2 pressure sensors
By-pass damper management
Mixing box management
Mixing box management with CO
Boost function
Adiabatic cooling management
Alarm management and diagnostic
Post ventilation
Clock program management
Remote On-Off
Digital input for PIR occupant sensor
Digital input for fire alarm
Digital input humidistat (only available on the FL series)
Heating / cooling selection by digital input
Hot water minimum thermostat
Remote display with internal temperature sensor
BMS Modbus protocol RS485
In the following diagrams is explained the summer-winter control logic
Tsp-Treg
Ventilation
Cooling modulation
= 2°C
Cooling
Cooling logic
Treg = regulation probe temperature (on supply air or room sensor on display)
Tsp = set point temperature
Te = external probe temperature
firmware 1.03
Electronic Control "LC2" User Manual

1 Control Features

sensor
2
sensor
2

2 Control logic

Ventilation
By-pass
= 2°C
Cooling modulation
Tsp-Te
+ By-pass
By-pass
+
Cooling
Figura A
By-pass
+
Heating
Heating modulation
+ By-pass
By-pass
= 2°C
Ventilation
Rev.11
Tsp-Treg
Heating
Heating modulation
= 2°C
Ventilation
Heating logic
EN
Tsp-Te
EN 3/ 15