Télécharger Imprimer la page

Eaton PowerXL DG1 VFD Serie Notice D'installation page 22

Masquer les pouces Voir aussi pour PowerXL DG1 VFD Serie:

Publicité

Instruction Leaflet IL040016EN
Effective January 2022
Factory-set control terminal functions
I/O connection
External wiring
Pin
Signal name
1
+10 V
2
AI1+
1
3
AI1–
4
AI2+
1
i
5
AI2–
6
GND
7
DIN5
8
DIN6
9
DIN7
10
DIN8
11
CMB
12
GND
13
24 V
14
DO1
15
24 Vo
16
GND
17
AO1+
18
AO2+
19
24 Vi
20
DIN1
21
DIN2
22
DIN3
23
DIN4
24
CMA
25
A
26
B
27
R3NO
28
R1NC
29
R1CM
30
R1NO
31
R3CM
32
R2NC
33
R2CM
34
R2NO
The above wiring demonstrates a SINK configuration. It is important that CMA and CMB are wired to ground (as shown by dashed line).
If a SOURCE configuration is desired, wire 24 V to CMA and CMB and close the inputs to ground. When using the +10 V for AI1, it is
important to wire AI1—to ground (as shown by dashed line). If using +10 V for AI1 or AI2, terminals 3, 5, and 6 need to be jumpered together.
1
AI1+ and AI2+ support 10K potentiometer.
22
EATON
www.eaton.com
Signal
Default setting
Ref. Output Voltage
Analog Input 1
0–10 V
Analog Input 1 Ground
Analog Input 2
4 mA to 20 mA
Analog Input 2 Ground
I/O Signal Ground
Digital Input 5
Preset Speed B0
Digital Input 6
Preset Speed B1
Digital Input 7
Emergency Stop (TI–)
Digital Input 8
Force Remote (TI+)
DI5 to DI8 Common
Grounded
I/O Signal Ground
+24 Vdc Output
Digital Output 1
Ready
+24 Vdc Output
I/O Signal Ground
Analog Output 1
Output Frequency
Analog Output 2
Motor Current
+24 Vdc Input
Digital Input 1
Run Forward
Digital Input 2
Run Reverse
Digital Input 3
External Fault
Digital Input 4
Fault Reset
DI1 to DI4 Common
Grounded
RS-485 Signal A
RS-485 Signal B
Relay 3 Normally Open
At Speed
Relay 1 Normally Closed
Run
Relay 1 Common
Relay 1 Normally Open
Relay 3 Common
At Speed
Relay 2 Normally Closed
Fault
Relay 2 Common
Relay 2 Normally Open
PowerXL DG1 Series VFD
Description
10 Vdc Supply Source
Voltage Speed Reference (Programmable to 4 mA to 20 mA)
Analog Input 1 Common (Ground)
Current Speed Reference (Programmable to 0–10 V)
Analog Input 2 Common (Ground)
I/O Ground for Reference and Control
Sets frequency output to Preset Speed 1
Sets frequency output to Preset Speed 2
Input forces VFD output to shut off
Input takes VFD from Local to Remote
Allows source input
I/O Ground for Reference and Control
Control voltage output (100 mA max.)
Shows the drive is ready to run
Control voltage output (100 mA max.)
I/O Ground for Reference and Control
Shows Output frequency to motor 0–60 Hz (4 mA to 20 mA)
Shows Motor current of motor 0–FLA (4 mA to 20 mA)
External control voltage input
Input starts drive in forward direction (start enable)
Input starts drive in reverse direction (start enable)
Input causes drive to fault
Input resets active faults
Allows source input
Fieldbus Communication (Modbus, BACnet)
Fieldbus Communication (Modbus, BACnet)
Relay output 3 shows VFD is at Ref. Frequency
Relay output 1 shows VFD is in a run state
Relay output 3 shows VFD is at Ref. Frequency
Relay output 2 shows VFD is in a fault state

Publicité

loading