Télécharger Imprimer la page

Eaton PowerXL DG1 VFD Serie Notice D'installation page 14

Masquer les pouces Voir aussi pour PowerXL DG1 VFD Serie:

Publicité

Instruction Leaflet IL040016EN
Effective January 2022
Input power and motor cable stripping lengths
Power wiring in inches (mm)
Frame
size
A1
FR0
0.39
(10)
FR1
0.39
(10)
FR2
0.59
(15)
FR3
0.59
(15)
FR4
0.98
(25)
FR5
1.10
(28)
FR6
0.98
(25)
Power connection tightening torque
Frame
Power wire
size
in-lb (Nm)
FR0
5.3 (0.6)
FR1
5.3 (0.6)
FR2
15.6 (1.8)
FR3
40 (4.5)
FR4
95 (10.7)
FR5
354 (40.0)
FR6
480 (54.2)
1
Strip the motor and power cables as shown above.
®
2
Both UL
and IEC tools may be used.
3
Applies to strained wire, solid wire, or ferrule installations.
14
EATON
www.eaton.com
B1
C1
5.12
0.39
(130)
(10)
1.77
0.39
(45)
(10)
1.77
0.59
(45)
(15)
1.57
0.59
(40)
(15)
2.56
0.98
(65)
(25)
6.10
1.10
(155)
(28)
4.72
0.98
(120)
(25)
12
Ground wire
Control wire
in-lb (Nm)
in-lb (Nm)
14 (1.6)
4.5 (0.5)
10 (1.1)
4.5 (0.5)
10 (1.1)
4.5 (0.5)
10 (1.1)
4.5 (0.5)
14 (1.6)
4.5 (0.5)
35 (4.0)
4.5 (0.5)
35 (4.0)
4.5 (0.5)
Motor wiring in inches (mm)
D1
A2
5.12
0.39
(130)
(10)
1.38
0.39
(35)
(10)
1.77
0.59
(45)
(15)
1.97
0.59
(50)
(15)
4.72
0.98
(120)
(25)
9.45
1.10
(240)
(28)
7.87
0.98
(200)
(25)
3
PowerXL DG1 Series VFD
B2
C2
3.15
0.39
(80)
(10)
1.77
0.39
(45)
(10)
1.57
0.59
(40)
(15)
1.57
0.59
(40)
(15)
2.56
0.98
(65)
(25)
6.10
1.10
(155)
(28)
4.72
0.98
(120)
(25)
D2
1.97
(50)
1.38
(35)
1.57
(40)
1.97
(50)
4.72
(120)
9.45
(240)
7.87
(200)

Publicité