Thermal Overload Protection - Dri-Eaz Dragon X2 Manuel Du Propriétaire

Masquer les pouces Voir aussi pour Dragon X2:
Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

WARNING: Replace hood to test
after each adjustment. Do not
operate the unit without the hood
securely in place. Serious injury
could result.
1. Open hood by removing sheet
metal screws and lifting. The hood
is hinged on one side.
2. The AIR ADJUSTMENT SHUTTER
(Fig. 2) is located on the burner
assembly. The factory setting is 5.
3. Loosen screw and rotate the
shutter in the appropriate direction:
a) A higher number corrects for
black smoke (allows more air into
the combustion chamber);
b) A lower number corrects for
white smoke (allows less air).
4. Tighten the shutter adjustment
screw, replace the hood, reattach
hood with the sheet metal screws,
and check for proper operation.
Tip: If the exhaust remains white even when adjusted to
0 (zero), there is probably water in the fuel. You may
need to replace the fuel filter and/or clean the fuel tank
(p. 6).
Always adjust the Dragon so that it produces clear
exhaust.

Thermal overload protection

The Dragon is automatically protected against internal
overheating. If the temperature of the heat exchanger
exceeds 175°F (79.4°C), the burner will automatically
turn off. The blower will continue to operate until the heat
exchanger has cooled. Once the exchanger has properly
cooled, the burner will automatically come back on and
the Dragon will resume normal operation.
For additional safety, the Dragon is also fitted with a high
temperature limit switch. If the heat exchanger reaches
205°F (96.1°C), the limit switch will shut down the
Dragon completely. The Dragon will not operate until the
limit switch is manually reset.
To manually reset the Dragon after a thermal
overload shutoff,
1. Open the hood: by removing sheet metal screws and
lifting. The hood is hinged on one side.
2. Turn the CONTROL KNOB to "Thermostat".
4. Press in the red HI-TEMP LIMIT switch (Fig. 1, D).
5. Replace the hood. The Dragon may now be restarted.
49-043 F 2011-06 Warranty 07-00424
Fig. 2: Air Adjustment Shutter and Bleed Valve
BURNER RESET BUTTON
Bleed valve
If the thermal overload switch or the high temperature
limit switch will not reset, contact the Dri-Eaz Service
Department at 800-932-3030 for assistance.
Note:
is restricted airflow. To help prevent thermal overload,
you should
Restarting after running out of fuel
If the Dragon runs out of fuel, a fuel cutoff sensor will
automatically shut the heater off and the BURNER
RESET BUTTON (Fig. 1, G) will glow red. The fan may
continue to cycle on and off until cooling is completed.
Follow these instructions for restarting.
Tip: It may be necessary to repeat these steps three or
four times until the fuel pump can refill the fuel lines and
provide sufficient fuel for heater operation.
1. Turn the CONTROL KNOB to the off position.
2. Refill fuel tank.
3. Turn the CONTROL KNOB to the "thermostat"
4. Open hood by removing sheet metal screws and
5. Press the BURNER RESET BUTTON once
5. If the pump turns off before the burner ignites, the
5
0
5
10
Air shutter adjustment screw.
Loosen to adjust shutter.
The most common cause of thermal overload
• Make ducting runs as straight and short as
possible
• Keep the ducting free of debris and
unobstructed
• Keep the air intake grill unobstructed
position.
lifting. The hood is hinged on one side.
thenreplace the hood. The fuel pump will begin
pumping fuel through the fuel line and the burner
should ignite after 20 seconds.
reset button must be pushed again. This occurs
Setting 5
(factory setting):
0–5000 ft.
Dri-Eaz Products, Inc.

Publicité

Table des Matières
loading

Produits Connexes pour Dri-Eaz Dragon X2

Ce manuel est également adapté pour:

F429Dragon x2 f429

Table des Matières