Step 8: Connect the Wallstations — Optional
If your lighting system uses wallstations, make the appropriate connections at the wallstation
using PELV (Class 2: USA) cabling .
NOTE: For procedures on how to install and address
wallstations, refer to the separate instructions included with
each device. Wallstations must be installed by a qualified
electrician in accordance with all local and national electrical
codes.
1. Daisy-chain the PELV (Class 2: USA) twisted pair for low-
voltage power wiring from the control unit to terminal
1 (common) and terminal 2 (12 V ) on up to three
wallstations.
2. Terminate the terminal 2 connection so that the control unit
supplies power to a maximum of three wallstations.
NOTE: To power more than three wallstations from one
control unit, install an external 12 V power supply (15 V
for CE/AU models). Refer to page 10 for instructions.
3. Daisy-chain the PELV (Class 2: USA) twisted pair data
link from the control unit to terminal 3 (MUX) and terminal
4 (MUX) on each wallstation .
WARNING! Make sure no bare wire is exposed after
making connections . The recommended installation
torque is 3 .5 in .-lbs . (0 .4 N•m) for PELV (Class 2: USA)
connections .
Control Unit Connected to Three Wallstations
GRAFIK Eye
3000 control unit
ZONE 2
CU WIRE ONLY
ZONE 4
ZONE 6
Class 2
USA
1 2 3 4
CLASS 2
HOT/LIVE
IEC
PELV
SSA
Each
terminal
can accept
2 #18 AWG
2
(1 .0 mm
)
wires
Data link:
4: MUX
3: MUX
Step 9: Connect Other Accessories — Optional
If your lighting system uses accessories other than wallstations (shade controllers, interface
devices, and power boosters), make the connections at the accessory using the appropriate
wiring .
For procedures on how to install and connect accessories, refer to the separate instructions
provided with each accessory .
Important Wiring Information
• Accessories must be installed by a qualified electrician in accordance with all local and national
electrical codes .
• Use properly certified cable as described in the instructions shipped with the accessory .
GRAFIK Eye
®
ZONE 1
ZONE 3
ZONE 5
NEUTRAL
PELV (Class 2: USA)
power wiring:
2: 12 V
1: common
3000 Series Control Unit Installer's Guide
Wallstation
Wallstation
4
4
3
3
2
2
1
1
Maximum of 1000 ft . (300 m) between the
GRAFIK Eye control unit and the third wallstation .
For longer distances or to power more than three
wallstations, see page 10 .
Each terminal can accept
2 #18 AWG (1 .0 mm
4
3
2
1
2 twisted pairs
#18 AWG
2
(1 .0 mm
)
Wallstation
4
3
2
1
2
) wires
Data link:
4: MUX
3: MUX
PELV
(Class 2: USA)
power wiring:
2: 12 V
1: common