During time programming the activation of TB, FTCI or FTCS will force the gate and the time count
to stop; as soon as the security devices are reset the time count and gate movement will continue.
2) Press the "PR" button (or activate either "TD" or the radio control) and keep it pressed until
the gate reaches the limited opening position. When the button is released the motor will stop.
It will continue the opening movement (and the work time count) after a period of 1 second.
3) When the opening travel limit is activated the motor will block but the work time count will carry
on in order to give a slightly higher time margin with respect to the exact manoeuvring time
4) Press the "PR" button (or activate either "TD" or the radio control): the work time count will end.
The warning light is still receiving power but the indicator lamp will now be flashing at slower
intervals: the pause time count has now started.
5) When the pause time is sufficient, press the "PR" button again (or activate either "TD" or the
radio control) the closing cycle will start and you will exit the programming procedure.
• When the unit is powered up; if the opening travel limit is active and automatic re-closing has
been selected the gate/door will close after the pause period has expired.
• When the unit is powered up with the gate/door not completely closed the logic will only allow
the opening command and not the closing command. The only exception occurs when the
opening travel limit is active.
• With the gate/door fully open, activating "FTCI" or "TA" will force a pause time reset.
• The limited opening command can only be used with the gate completely closed; it is not pos-
sible to give two successive limited opening commands. If the FTCI is activated after a limited
opening command has been received during the closing cycle the gate opening will still be
limited (it will not open completely).
INDICATOR LIGHT FUNCTION MODES
The (24Vac, 3W) indicator lamp output is used to indicate the gate/door status:
• When the gate/door is completely closed: Indicator lamp off
• Gate/door moving in the opening direction: Indicator lamp on
ALARM INDICATIONS
1) Wrong parameters in EEPROM memory
If there is a data read error from EEPROM the warning lamp will indicate the error by flashing inter-
mittently: the system will be blocked. You will have to enter work time programming to correct the
error. Pressing the "PR" button will force the LED "LPR" to flash straight away.
2) Simultaneous travel limit activation
Simultaneous travel limit activation will cause the programmer to block as long as the problem
exists. The warning light will stay on for 3 seconds and will be activated every 6 seconds.
When the travel limits have been freed an automatic reset will occur and normal operation will return.
***** READ THE FOLLOWING NOTES CAREFULLY *****