Riello Elettronica CARDIN PRG384 Mode D'emploi page 11

Table des Matières

Publicité

Les langues disponibles
  • FR

Les langues disponibles

LOGIC CARD FUNCTIONS
Legend
PR:
Programming button
LPR:
Programming LED
D1:
Function selection dip-switch
Indicator leds: TB-FTCS-FTCI
Safety device status
Lit leds indicate safety devices at rest or
jumped if not used
Leds off indicate that the safety devices
are functioning incorrectly (damaged), in
the process of intervening (working) or
incorrectly jumped (unused safety devices)
EXTRACTABLE LOGIC CARD FUNCTIONS
1)
Work time:
The door is considered completely open (and therefore automatic reclosing is carried out) even
when the opening time has ended and the FCA travel limit has not intervened; program the opening
times so as to leave a margin greater than the time required to reach the opening travel limit FCA.
2)
Pause time:
Set the pause time according to the characteristics of the motor; if that time is very brief the gate
will carry out a rapid travel direction inversion as soon as it reached the completely open position.
DIP-SWITCH SETTINGS (D1)
DIP 1:
On =>
Off =>
DIP 2:
On =>
Off =>
DIP 3:
On =>
Off =>
Note: to set the dip-switches; turn off the power to the programmer, change the settings and then
switch the power back on.
WORK TIME PROGRAMMING (LIMITED OPENING, OPENING AND PAUSE)
1) With the door completely closed, press and hold down the "PR" button for 4 seconds. The led
Drawing number :
"LPR" will be off to start with and will then start to flash rapidly indicating that the programming
mode has been entered. The indicator light will flash intermittently at the same frequency as
the indicator led. Release the "PR" button.
Product Code :
YPR302
Note: if you press the "PR" button and the led "LPR" lights up straight away (and remains lit) it
Draft :
P.J.Heath
means the programmer is not in the completely closed state and you cannot enter the program-
ming mode. Switch the power off and on again.
If you press the "PR" button and the led "LPR" flashes it means that a memory data error has
CARDIN ELETTRONICA S.p.A - 31020 San Vendemiano (TV) Italy - via Raffaello, 36 Tel: 0438/401818
been encountered; the programmer will be blocked and you will have to reprogram the work times.
(see paragraph "alarm conditions").
If the security devices (TB, FTCI, FTCS) are not at rest or the opening travel limit is activated, time
programming will not be enabled.
automatic re-closing enabled.
automatic re-closing disabled.
"manual mode" activated.
"manual mode" disactivated.
TD mode: "open-block-close-block"
TD mode: "open-close" with inversion only during the opening stage.
DC0325
Date :
05-03-2001
TCS
D1
LPR
PR
3 2 1
ON
PR
Description:
Logica PRG401 (cs1112AB.01)
11
FTCI FTCS TB
0-120 seconds
0-120 seconds
6

Publicité

Table des Matières
loading

Table des Matières