AC INPUT
Input Voltage range
Max Input Current
Nominal Input Frequency
Input Power Factor
Input Phases
DC OUTPUT
Nominal DC Output Voltage
Nominal DC Output Current
Nominal Output Power
AC-DC conversion efficiency
Power Up Time
Line Regulation
Ripple
Noise
ENVIRONMENT
Operating temperature range
Cooling
Relative Humidity
DIMENSIONS
UNIT Dimensions(WxLxH)mm
UNIT Net Weight (Kgs)
STANDARD COMPLIANCE
Certification
Safety
EMC
The guarantee conditions may vary depending on the country where the battery charger  is sold
so please check with your local Legrand sale representative for validity and duration.
14
160V-280V
4.6Arms Max.
50Hz/60Hz±10%
> 0.85
Single phase
273Vdc±3Vdc (No Load)
2,5A (5A max)
1000W Max
>0,7 at full load
< 75ms
≤ 1% (No Load)
~ ± 5V
~ ± 3V
0°C ~ 40°C
Forced air ventilation by DC fan
10% ~ 90% (without condensation)
166 x 282 x 86
IEC 60950-1
EN 61000-6-4, IEC 61000-3-2, IEC 61000-3-3,
EN 61000-6-2 (EN 61000-4-2, EN 61000-4-3,
EN 61000-4-4, EN 61000-4-5, EN 61000-4-6,
EN 61000-4-8, EN 61000-4-11)
WARNING : This is a product for commercial
and industrial area.In a different environment-
installation restrictions or additional measures
may be needed to prevent disturbances

4 Specifications

3.2
CE

5 Warranty