Water
hardness
DOUBLE 35 RED Ejector
in
F
litres
°
water
20
10.500
25
8.400
30
7.000
35
6.000
40
5.200
45
4.600
DEFINITION OF THE REGENERATION FREQUENCY FOR THE TIME SYSTEM :
E.g.:
Supposing that for DOUBLE 85 a daily consumption of 4200 litres is required (with hardness of 30°F)
17.000:4200=4 the number to set (in this case regeneration takes place every 4 days).
CORRESPONDING REGENERATION TIMES:
1 C =
6 minutes backwash
2 C =
30 minutes brine suction
3 C =
30 minutes slow rinse
4 C =
8 minutes rapid rinse
Height of floater = 500 mm
SYSTEM VOLUME - VOLUME TIME
N.B.
The number of litres of water to be set on the display is 1/100 that found in the table. E.g. value in table is 17.000.
The value to be set (17.000:100) = 170.
The litres are counted with a pulse every 100 litres, without changing the actual quantity of water.
N.B.
The litres of softened water shown in this table are obtained with intake water with a total hardness of max. 45°F
and salinity not exceeding 500 PPM, without oils, colourless and without turbidity.
Water consumption per regeneration is calculated as a function of the following parameters:
- time of each phase
- water flowrate at the drain
- operating pressure
TABLE FOR SOFTENED WATER VOLUMES IN RELATION TO HARDNESS
(regeneration times and floater position)
DOUBLE 50 RED Ejector
floater
time
litres
H mm
1'
water
100
13.750
100
11.000
100
9.100
100
7.800
100
6.800
100
6.100
volume of water treated (softened)
volume of water for daily consumption
DOUBLE 65 RED Ejector
floater
time
litres
H mm
1'
water
260
20.600
260
16.400
260
13.700
260
11.700
260
10.300
260
9.100
37
floater
time
H mm
1'
150
150
150
150
150
150