If the drive is installed in areas where debris and small animals or insects are likely
to enter the drive, an additional Air Screen Kit should be installed. See Accessories
page for ordering information.

Wire Routing

To ensure the best protection from interference with other devices, please observe the
following precautions:
Separate input power and motor
wiring by at least 8" (20.3 cm)
Input
power
GND
Service Entrance
When possible DO NOT run drive input
power or motor wires in parallel with house wiring.
Avoid running out-building wires in parallel with motor wires.
Output lead to motor to
exit house as soon as possible.
Motor
GND
Panel
GND
SubDrive/MonoDrive
DO NOT run input power
and motor wires together.
Separate by at least 8" (20.3 cm)
GND
GND
Motor
8"
GND
20.3 cm
Input
power
Pump
Motor