Installation Instruction

General installation instructions

1. Danfoss self-limiting heating cables are only
for safe (non hazardous) areas.
2. Measure the insulating resistance of the
heating cable immediately before the installation
is begun.
3. Make sure that the necessary materials are
present at the building site.
4. Remove any sharp objects and irregularities
on the pipe system, so the heating cable are not
damaged.
5. Finished or painted pipes or containers must
be completely dry when installing. The heating cable
must only be used in the manners recommended by
Danfoss and should be properly connected to the
main electrical source.
6. Connection of the heating cable must be
done by an authorised electrician according to local
legislation.
7. The maximum effect for the different installa-
tions and operating effects must be observed.
8. The heating cable must be protected against
excess strain and tension.
9. The surface onto which the heating cable is to
be installed must be non-combustable, clean and free
from sharp objects.
Storage of self-limiting cables
Heating cables and connecting leads must
be kept in a clean and dry place.
Avoid contact with chemicals and petro-
chemical products during storage of the cables.
Do not expose the heating cables to me-
chanical strain.
The storage temperature may not drop
below -40°C and may not exceed +60°C.
Are the heating cables and connecting
leads kept in moist rooms or at building sites, they
must be protected against moisture - also during
storage for a short period (e.g. when installing the
cable terminal).
6 | © Danfoss | FEC | 2019.04
ECiceguard 18 Readymade
not be less than 50 mm. The cable must only be bend
on the flat side.
accordance with local electricity legislation.
an isolation switch or a similar overload protection
device.
required.
recommend to switch off the heating cable, if this is
longer than 3 m, i.e. by using a ECtemp thermostat
(see „Regulation").
become stiff and difficult to work with. This problem
can be solved by connecting the cable shortly to the
mains
ured before and after installation.
made evident by caution signs or markings at the
power connection fittings and/or frequently along
the circuit line, as well as being stated in any electrical
documentation following the installation.
10. The heating cables bending diameter must
11. The heating cables screen must be earthed in
12. The power circuit must be equipped with
13. Residual current device (RCD) protection is
14. To reduce energy consumption we strongly
15. At low temperatures the heating cable can
16. The cable insulation resistance must be meas-
17. The presence of a heating cable must be
088L8004 / VIMSB102