3 Connection
This chapter is about terminal assignment and will present some wi-
ring examples.

3.1 Terminal assignment

Litz contact only by means of connector sleeves with insulating
enclosures for reasons of shock protection according to EN 61010.
Do not otherwise assign contacts that have been left unassigned ex
factory. We recommend to screen all sensor terminal leads and to
ground the shield on one side. Shields on both sides are recommen-
ded in case of RF interference or in case of equipotential bonding
over long distances. The sensor leads should not be in the same
phase winding as the mains supply and the output contact leads.

3.2 Inputs and outputs

Signal
±200 V
±20 V
±10 V
±100 mV
±20 mA

3.3 Voltage supply connection

There are several options for operation supply. Power supply must
be fed in via the recommended external fuse.
Operating voltage
85...265 VAC, (50/60 Hz) and 100...300 VDC
21...53 VAC, (50/60 Hz) and 10.5...70 VDC
www.baumer.com
Resolution
Input resistance
0.1 V
1 M
0.01 V
1 M
1 mV
1 M
0.1 mV
100 M
0.01 mA
20
PA200
External protection
M 100 mA
M 500 mA