Tapeswitch PRSU/M2SI Manuel D'utilisation page 8

Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

Technical Data
Switching capacity
to AC 15
NO contacts:
to DC 13
NO contacts:
Electrical life
at 5 A, AC 230 V cos j = 1:
Permissible operating frequency
1. safety function:
2. safety function:
Short circuit strength
max. fuse rating:
Mechanical life:
Semiconductor monitoring output
(not safety):
General Data
Nominal operating mode:
Temperature range
Operation:
Storage:
Altitude:
Clearance and creepage distance
rated impuls voltage /
pollution degree:
EMC
Electrostatic discharge (ESD): 8 kV (air)
HF irradiation:
Fast transients:
Surge voltage
between
wires for power supply:
between wire and ground:
HF-wire guided:
Interference suppression:
Degree of protection
Housing:
Terminals:
Housing:
Vibration resistance:
Klimate resistance:
Terminal designation:
Wire connection:
Wire fixing:
Mounting:
Weight:
UL-Data
The safety functions were not evaluated by UL. Listing is accom-
plished according to requirements of Standard UL 508, "general use
applications"
Switching capacity:
Ambient temperature 55°C
Ambient temperature 40°C:
Wire connection::
Terminal:
3 A / AC 230 V
IEC/EN 60 947-5-1
2 A / DC 24 V
IEC/EN 60 947-5-1
> 1.5 x 10
switching cycles
5
max. 1800 switching cycles / h
max. 360 switching cycles / h
6 A gL
IEC/EN 60 947-5-1
10 x 10
6
switching cycles
1 per safety function
max. 50 mA DC 24 V, plus switching
continuous operation
- 15 ... + 55 °C
- 25 ... + 85 °C
< 2.000 m
4 kV / 2
IEC 60 664-1
IEC/EN 61 000-4-2
10 V / m
IEC/EN 61 000-4-3
2 kV
IEC/EN 61 000-4-4
1 kV
IEC/EN 61 000-4-5
2 kV
IEC/EN 61 000-4-5
10 V
EN 61 000-4-6
Limit value class B
EN 55 011
IP 40
IEC/EN 60 529
IP 20
IEC/EN 60 529
thermoplastic with VO behaviour
according to UL subj. 94
Amplitude 0,35 mm
Frequency 10 ... 55 Hz, IEC/EN 60 068-2-6
15 / 055 / 04
IEC/EN 60 068-1
EN 50 005
DIN 46 228-1/-2/-3/-4
captive slotted screw
DIN rail
IEC/EN 60 715
approx. 275 g
Pilot duty B300, R300
5A 250Vac Resistive or G.P.
5A 24Vdc Resistive
Pilot duty B300, R300
8A 250Vac Resistive or G.P.
8A 24Vdc G.P.
60°C / 75°C copper conductors only
AWG 28 - 12 Sol/Str Torque 0.5 Nm
Troubleshooting
Failure
LED "ON" does not light up
LED "ERR" flashes
in relation 1:1
LED "ERR" flashes
in relation 4:1
LED "ERR"
continuously on
Maintenance and Repairs
- The device contains no parts that require maintenance.
- In case of failure, do not open the device but send it to manufacturer
for repair.
8
Potential cause
- Power supply A1+/A2
not connected
- Under- or overvoltage
(check power supply A1+/A2)
- external failure (see flashing code)
- system error
(if cannot be removed after restart
unit must be replaced)
03/2021 DE-EN-FR

Publicité

Table des Matières
loading

Table des Matières