Supplementary Control And Monitoring Elements; Monitoring Contacts/Door Contacts - EFF EFF 1340-10 Mode D'emploi

Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

Control functions / monitoring contacts
red
green
yellow
Key-operated switch positions:
Right-hand momentary contact =
Escape door lock "on", Door monitoring "on"
Left-hand momentary contact =
Escape door lock "off", Door monitoring "off"
If the functional status of the system is switched to emergency
unlocking, this status can be cancelled by briefly turning the key-
operated switch to the left. This is only possible if the cause of the
„Emergency unlocking" signal activated by the emergency switch
or other external contacts has been remedied and reset (see
section Cancel/Relocking).
The following inputs for external appliances are provided for at the
Escape Door Control Terminal 1340-10(11).
Locking elements
Surface holding magnet 827 (max. 2 magnets, only for parallel
operation)
or Surface holding magnet 828 (max. 2 magnets, only for parallel
operation)
or Surface holding magnet 829 (1 magnet)
or Electric panic opener 3150 (max. 2 openers, only for parallel
operation)
or Escape door lock release 331 RR AK RR (max. 2 releases,
only for parallel operation)

Supplementary control and monitoring elements

Central indicator board 725
Door monitoring contact (e.g. cone contact 10400)
Fire alarm (line control)
external display elements for operating statuses (door unlocking,
door locking, door emergency unlocking and sabotage)

Monitoring contacts/door contacts

! When using surface holding magnets or panic openers 3150 as
a door locking element, it is necessary to mount an external
door contact in the door element. This door contact informs the
escape door control system that the respective escape door
has been closed to guarantee a functional locking process.
When using the escape door lock release 331 RR AK RR as a
14
LED displays
red =
Escape door in locked
status, Door monitoring
active
green =
Escape door in unlocked
status Door monitoring not
active
green/yellow =
Escape door in emergency
unlocked statusSignal
"emergency unlocked
status"
green/yellow or
red/yellow =
Sabotage
Signal "Sabotage"

Publicité

Table des Matières
loading

Ce manuel est également adapté pour:

1340-11

Table des Matières