Thank you for purchasing our "intelligent" quad
photoelectric beam.
This unit will provide long and dependable service
when properly installed.
Please read the Instruction Manual carefully to ensure
correct and effective use.
This sensor is designed to detect intrusion events
and initiate alarm. It is not a burglary- preventive
device.
Vanderbilt is not responsible for any kind of
damage, injury or losses caused by accident,
theft, force majeure (including inductive surge by
lightning), abuse, misuse, abnormal usage, faulty
installations or improper maintenance.
Product description
The Vanderbilt photoelectric beam sensor (IS443,
IS444 and IS445) consists of an infrared transmitter
and receiver.
It is designed to be "AND" gated - an alarm is initiated
only when all four (quad) stacked beams are
interrupted simultaneously.
Alarm is not initiated when up to three beams are
interrupted by e.g. insects or falling leaves.
In addition, four beam frequency channels are
available to prevent cross-talk when multiple units are
stacked or lined up.
Due to the Programmed AGC function the sensitivity
is automatically increased in bad weather conditions
in order to deal with fog, rain or frost.
1

Parts description

Cover
A
-
View finder
B
-
Mirror
C
-
Horizontal fine adjustment screw
D
-
Vertical adjustment screw
E
-
Terminals
F
-
Tamper switch
G
-
Gain lock switch (Receiver only)
H
-
Functions indications (see R to AF)
I
-
Mirror
J
-
Adjustment dial
K
-
Shading plate
L
-
Mounting plate
M
-
Bracket
N
-
Knockout
O
-
Pole cover
P
-
Knockout
Q
-
Operation LED
R
-
Beam power (set to H at factory)
S
-
Beam channel (frequency 1-4; 1ch. set at
T
-
factory)
Sensitivity attenuation LED
U
-
Alarm LED
V
-
Beep (Alignment tone) switch (set to OFF at
W
-
factory)
Response time adjustment (set to 0.05sec.
X
-
at factory)
Monitor jack
Y
-
Memory LED
Z
-
Beam channel (frequency 1-4; set to 1ch. at
AA -
factory)
Alarm output selector (set to N/C at factory)
AB
-
Memory selector (set to Manual at factory)
AC
-
Enviromental output selector
AD
-
(set to N/C at factory)
Environmental output terminal
AE
-
Remote control input terminal
AF
-
Installation Manual for IS443 / IS444 / IS445
Wiring distance between sensor and
control panel
IS443
AWG22 (ø0.65mm)
AWG20 (ø0.8mm)
AWG18 (ø1.0mm)
AWG17 (ø1.1mm)
AWG16 (ø1.25mm)
AWG15 (ø1.4mm)
AWG14 (ø1.6mm)
IS444
AWG22 (ø0.65mm)
AWG20 (ø0.8mm)
AWG18 (ø1.0mm)
AWG17 (ø1.1mm)
AWG16 (ø1.25mm)
AWG15 (ø1.4mm)
AWG14 (ø1.6mm)
IS445
AWG22 (ø0.65mm)
AWG20 (ø0.8mm)
AWG18 (ø1.0mm)
AWG17 (ø1.1mm)
AWG16 (ø1.25mm)
AWG15 (ø1.4mm)
AWG14 (ø1.6mm)
The maximum wiring distance when two or more
sets are connected is the above- mentioned value
divided by the number of sets.
The signal line can be wired to a distance up to
1000m with AWG22 (dia 0.65mm) telephone
wire.
Installation height
In most cases, the beam should be installed at a
height of 70cm to 90cm.
Take into consideration the beam spread of each
model type in order to avoid potential reflection from
the ground surface or nearby objects. (see table
Mounting
The units can be easily mounted on a pole or an even
surface.
- Alignment by mirror adjustment.
Using the adjustment dial and adjustment screws,
the mirror can move horizontally (±90°) and
vertically (±10°), allowing the sensor to work in all
directions.
Remove cover; the screw is at base of the cover
Loosen any screws that fix the sensor body to the
mounting plate and slide the mounting plate
downwards to detach it.

Wall mounting

Locating
Place the mounting plate on the wall as a drilling
template and mark the screw holes (allow for 20mm
12V
24V
space above the plate and 25mm below the plate.
120m
1100m
This will provide for easy detachment of the cover
after installation.)
210m
1900m
Drill holes in the wall.
Wooden wall: ø 3mm
310m
2800m
Concrete wall: Refer to the specifications of the
securing plug used.
380m
3400m
Install the sensor.
Insert a mounting screw; about 15mm of the screw
500m
4500m
length should be projecting.
670m
6000m
Install mounting plate on screws.
Insert cable.
840m
7600m
Tighten screws.
Connect terminals.
Attach cover.
12V
24V
Seal the cable hole to prevent insects from
penetrating the unit.
110m
1000m
The unit cannot be installed on an outlet box.
However, an outlet box can be used to provide cable
190m
1700m
space.
280m
2500m

Pole mounting

340m
3000m
Drill cable hole in pole. Insert cable.
- The unit can be mounted onto a ø38-45mm O.D.
450m
4100m
(outside diameter) pole.
- Drill a ø13mm hole through the pole where the unit
610m
5500m
will be mounted for wiring.
Remove all drilling chips and file all sharp edges
760m
6800m
around the hole to prevent rough edges from
damaging the cable.
A rubber grommet or bush may be used if desired.
12V
24V
Install sensor on pole.
Attach U-brackets to pole and secure on mounting
100m
900m
plate with screws.
160m
1500m
Attach sensor body.
Insert cable.
250m
2200m
Connect terminals.
Attach covers. (Break knockouts on cover and pole
300m
2700m
cover to adapt to pole diameter and configuration.)
Pole mounting back to back
400m
3600m
Attach four U-brackets to poles in two pairs, one on
top of the other, facing in opposite directions (see
530m
4800m
illustration).
660m
6000m
)
3
.
6
6
B
4
A
4
4
B
4
C
C
4
A
5
5
B
5
C