Fan:
Minimum mounting height 2.3m.
As far away as possible from the main source of air replacement to
ensure airflow across the room (eg. opposite the internal doorway).
Near the source of steam or fumes.
Not where ambient temperatures are likely to exceed 50
a cooker hob or eye level grille.
If installing in a room containing a fuel-burning device which has a
non-balanced flue, it is the installer's responsibility to ensure that
there is enough replacement air to prevent fumes being drawn down
the flue, when the fan is operating on maximum extract. Exhaust air
must not be discharged into a flue used for exhausting fumes from
appliances supplied with energy other than electric. Requirements of
all authorities concerned must be observed for exhaust air discharge.
When intended for use in possible chemical corrosive atmospheres,
consult our Technical Services Department.
If any vertical ducting is installed a condensation trap must be
fitted.
When fitting horizontal ducting, ensure it is sloping away from fan.
An electrical product in a shower room or bathroom must be so
situated that it cannot be touched by persons making use of the bath
or shower.
0
C, or above