Fan Trouble Shooting - Canarm GSQ-D Série Mode D'emploi

Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

GSQ-D SERIES
GSQ-D EC SERIES
If your unit
contains the
ECsmart Motor
please follow
these wiring
diagrams:
PRE-START INSPECTION
START-UP
Turn the fan on and inspect for the following:
1.
Direction of rotation.
2.
Improper motor amperage.
3.
Excessive vibration.
4.
Unusual noise.
If a problem is discovered shut off the fan and refer to the section on troubleshooting to discover the cause of the problem. The fan
should be inspected after 30 minutes, 8 hours and 24 hours of operation to ensure all fasteners are tight and belts are properly tensioned
and aligned.
MAINTENANCE
Disconnect and secure to the OFF position all electrical power to the fan prior to inspection or servicing. Failure to comply with this safety
precaution could result in serious injury or death.
1.
Ventilator should be checked at least once a year. For critical or severe applications a routine check every two to three months is
suggested.
2.
A periodic inspection of all fasteners should be carried out to ensure they have not loosened due to vibration. Particular attention
should be paid to fasteners attaching the wheel to the shaft.

FAN TROUBLE SHOOTING

WARNING: Make sure the unit is not capable of operation during reparation.