420010343802 Blu 700.1 ÷ 1200.1 P AB V.C. Low Nox
EN
ADJUSTMENT OF GAS MINIMUM PRESSURE SWITCH
Unscrew off and remove cover M. - Set regulator N to a value equal to 60% of gas
nominal feed pressure (i.e. for nat. gas nom. pressure = 20 mbar, set regulator to a value
of 12 mbar.Screw up cover M
ADJUSTMENT OF THE AIR PRESSURE SWITCH
Unscrew screws A and B and remove cover C.- Set the pressure switch to the minimum
by turning regulator D to position 1.
- Start the burner and keep in low flame running, while checking that combustion is
correct. Through a small cardboard, progressively obstruct the air intake until to obtain
a CO2 increase of 0,5÷0,8% or else, if a pressure gauge is available, connected to pres-
sure port E, until reaching a pressure drop of 1 mbar (10 mm of W.G.). - Slowly increa-
se the adjustment value of the air pressure switch until to have the burner lockout.
Remove the obstruction from the air intake, screw on the cover C and start the burner
by pressing the control box rearm button.
With the burner switched off, connect a DC microammeter with a 0÷50 or 0÷100 µA dial. When the burner is run-
ning, and is properly adjusted, the value read must be steady and never be smaller than 1,5 µA.
7
The burners are produced with connections suitable for power supply 400 V three-phase.
The burners with electric motors of an output lower or equal to 7,5 kW can be adapted to 220-230 V (please follow the
instructions on the backside); motors with higher output can only work 380-400 V three-phase.
In case of request of burners different from the above mentioned standard, it is recommended to make specific mention
in the order.
Instructions: how to adapt electric motors of an output lower or equal to 7,5 kW to 220-230 V power supply
It is possible to change the voltage of the burner by operating as follows:
1. change the connection inside the electric box of the motor, from star to delta (see picture);
2. change the setting of the thermal relay, referring to the absorption values indicated in the motor nameplate. If
necessary, replace the thermal relay with another one of suitable scale.
FLAME DETECTION SYSTEM CHECK
DESCRIPTION OF THE CONTROL PANEL OF THE BURNER
I
0
1
min. 1,5 µA
LME11/LME21-22
1
1 - fuse
2
2 - termal lock-out lamp
3 - 1 st. stage working lamp
3
4 - 2 nd. stage working lamp
4
5 - high-low flame switch
5
6 - main switch I / O
7 - reset key
6
pag.16