AEROTOP SPLIT
Preliminary Actions
This procedure must be performed by qualifi ed personnel, in accordance with the requirements of F-Gas Regulation.
- Installation must be pre-cleaned
(limpid appearance of the system liquid, without visible impurities)
- If present, tank must be pre-cleaned, too.
- Proper water quality (hardness between 12 °F / 6,5 °dH and 20 °F / 11 °dH;
pH between 6.6 and 8.5)
1
- Minimum clearances between external unit / internal unit
and walls / fl oors / ceilings guaranteed (see image below)
- System Interface placed at least 1,5 m from the fl oor and far from heat sources,
drafts or opening to the outside
- Outdoor Sensor placed on the north-facing wall of the building, at least 2.5 m
from the ground and away from direct sunlight
- External unit must be installed on a perfectly horizontal and resistant base,
in an easily accessible place to allow installation and maintenance operations
- External unit must be placed at least 200 mm above the usual level of fallen snow,
2
in case of installation in a location with abundant snowfall
- External unit placed where noise and air discharged do not disturb the neighbors
- Protective screen placed, in case of strong wind presence
- No obstacle must limit the air infl ow through the fan
- Internal unit placed in a compartment at home in an easily accessible place
3
to allow installation and maintenance operations
- Internal unit properly fi xed to the wall or anchored to the ground
Minimum distances to installation (mm)
12 / GB
1000
150
150
300
Assessment
150
150
x*
150
150
* x = 0 mm with hydraulic connection
kit right / left
* x = 80 mm with hydraulic connection
kit on top
Comments
500
800