Putting into operation
7.2 Setting the air flow
The air flowrates from the Ubiflux W180 are set ex factory at
50, 75, 100 and 150 m
/h. The performance and the energy
3
consumption of the Ubiflux depend on the pressure drop in the
duct system as well as on the filter resistance.

Important:

Setting : is 0 or 50 m
/h (not for 3-way switch),
3
Setting 1 : must always be lower than setting 2,
Setting 2 : must always be lower than setting 3,
Setting 3 : adjustable between 50 and 180 m
If these conditions are not complied with, the air flowrate of the
higher mode will automatically be adjusted.
For modifying the air flowrates in the settings menu, see § 6.3.

7.3 Other settings installer

Various other settings of the Ubiflux can also be modified. How
to modify these is explained in §6.3.

7.4 Factory setting

It is possible to reset all modified settings back to factory set-
ting in one go.
All modified settings will be at the values they had when the
Ubiflux was supplied from the factory; all message codes / fault
codes will be erased from the service menu as well.
The filter message will not be reset!
/h.
3
Ubiflux W180 / W180+
Chapter 7
press > 10 sec.
simultaneously
3 sec. displayed
operating mode
21