6 - CONFIGURING THE UNIT
Access level
No.
Description
1
290
Opening of the heating coil three-way valve
1
291
Opening of the three-way valve on the cooling coil or mixed coil
1
294
Progressive humidifier percentage
1
295
Fan rotation speed
1
296
Fresh air percentage
1
297
Electric heater percentage
300
Condensation unit 1
301
Short-cycle protection time countdown for condensation unit 1
302
Condensation unit 1 number of start-ups
303
Condensation unit 1 operating-hour meter
304
Condensation unit 2
305
Short-cycle protection time countdown for condensation unit 2
306
Condensation unit 2 number of start-ups
307
Condensation unit 2 operating-hour meter
1
320
Electric heater stage 1
1
321
Operating-hour meter for electric heater stage 1
1
322
Electric heater stage 2
1
323
Operating-hour meter for electric heater stage 2
1
330
Fan control state
1
331
Fan operating-hour meter
1
350
Indication of the critical faults
1
351
Operating-hour meter indicating the critical faults
1
352
Indication of the non-critical faults
1
353
Operating-hour meter indicating the non-critical faults
1
360
Fan on request 
1
361
Temperature setpoint shift request 
1
362
Warm-up
1
363
Activation time delay for the compressor stages
1
365
CCU CONTROLLER software version number
1
370
Temperature measured by the controller
1
371
Temperature received by ModBus
1
372
Temperature measured at 2-10 V input
1
373
percentage on external signal
1
570
SO order number
1
571
OF number
PERCENTAGE FOR ANALOGUE OUTPUTS
STATE OF THE COMPRESSOR CONTROLS
STATE OF THE ELECTRIC HEATER CONTROLS
STATE OF THE FAN CONTROLS
STATE OF THE FAULT SUMMARY CONTROLS
STATE OF THE FAN CONTROLS
TIME DELAY COUNTDOWN
VERSION NUMBER
TEMPERATURE FOR CONTROL
ORDER NUMBER
Unit
Display condition
%
P08 = 1 or 3
%
(P07 = 1 or 3) or (P09 = 1 or 3)
%
P10 = 1
%
P02 > 9
%
P11 = 1
%
P08 = 2 or 3) and (P16 = 3 or 4)
Off/On
P16 = 2
h
P16 = 2
Off/On
P16 = 2 or 4
h
P16 = 2 or 4
Off/On
h
Off/On
h
Off/On
h
Off/On
P01 = 2
Off/On
P31 = 2 or P32 = 2
mins
mins
P17 = 3 or 4
°C
P207 = 1 and P207=2
°C
P207 = 1
°C
(P07>0 or P08>0) and P207=2
%
(P07>0 and P08=0) and P207=3