Pulsar
Output personalization
Function
Output voltage
(1)
Frequency
converter
(1)
Output frequency
Transfer to the
bypass AC input
(1)
(1)
Overload level
(1) These parameters may be modified only when the UPS is OFF. Detailed comments are available in the Personal
Solution-Pac software.
ON/OFF personalization
Function
Start on battery power Enabled
Automatic restart
Energy savings
Detection of phase/
neutral inversion
(SWF)
Battery personalization
Function
Battery test
Low-battery warning
Selection of the
backup time
Battery protection
against excessive
discharges
4.4

Personalization using external software

Insert the Solution-Pac CD-ROM in the drive.
On the first navigation screen, select "Point to Point solution" and follow the instructions on how to install the
Personal Solution-Pac software.
Then select "Settings", "Advanced settings" and "UPS settings". Note that the Linux/Unix/MacOS versions of the
Personal Solution-Pac software do not offer this possibility.
4 — 2
Factory Setting
120 Volts AC
Disabled
(1)
Automatic selection
Bypass AC power
must be within
tolerances
100%
Factory Setting
Enabled
Disabled
Enabled
Factory Setting
Weekly test
20%
Automatic detection
of number of battery
modules
Enabled
Access to Maintenance and Personalization Data
Other available
Comments
settings
100 to 127 Volts AC
The connected devices are never trans-
Enabled
ferred to the bypass.
User selectable only if the frequency-
50 or 60 Hz
converter function is enabled.
Bypass AC power
may be outside
tolerances
30 / 50 / 70%
Alarm if threshold is overrun.
Other available
Comments
settings
Disabled
The UPS restarts automatically when AC
Disabled
power returns.
When function enabled, battery shuts down
Enabled
when power drops to <5%.
Neutral inversion (SWF) When function
Disabled
enabled, the UPS remains OFF if the
system detects phase/neutral inversion.
Other available
Comments
settings
No test / daily test /
monthly test
0 to 100%
Adjustable in 1% steps.
13 to 200 Ah
Excessive discharges when function
Disabled
disabled, MGE Office Protection Systems
warranty no longer applies.
E N G L I S H
86-86700-00 A01