Faults / Solutions; Possible Causes - Sime Mack 4Sp Manuel D'entretien

Table des Matières
Les langues disponibles

Les langues disponibles

6. FAULTS / SOLUTIONS

Here below you can find some causes and the possible solutions for some problems that could cause a fail-
ure to start or a bad working of the burner.
A fault usually makes the lock-out lamp light which is situated inside the reset button of the control box
(3, fig. 1, page 1).
When lock out lamp lights the burner will attempt to light only after pushing the reset button. After this if the
burner functions correctly, the lock-out can be attributed to a temporary fault.
If however the lock out continues the cause must be determined and the solution found.
FAULTS
The green led on
the control box is
off and the burner
does not start.
The green led on
the control box is
on and the burner
remains in the pre-
purge phase.
B u r n e r r u n s n o r-
m a l ly i n t h e p r e -
purge and ignition
cycle and locks out
after 5 seconds ca.
Burner starts with
an ignition delay.
WARNING
The manufacturer cannot accept responsibility for any damage to persons, animals or property due to error in
installation or in the burner adjustment, or due to improper or unreasonable use or non observance of the
technical instruction enclosed with the burner, or due to the intervention of unqualified personnel.
2686

POSSIBLE CAUSES

Lack of electrical supply.
The connections in the control box are
wrongly inserted.
The photoresistance sees false light.
The photoresistance is dirty.
The photoresistance is defective.
Flame moves away or fails.
The ignition electrodes are wrongly
positioned.
Air output is too high.
Nozzle dirty or worn.
Check presence of voltage in the
L1 - N clamps of the 7 pin plug.
Check the conditions of the fuses.
Check that thermostat limit is not
lock out.
Check and connect completely all the
plugs.
Eliminate the light.
Clear it.
Change it.
Check pressure and output of the fuel.
Check air output.
Change nozzle.
Check the coil of solenoid valve.
Adjust them according to the
instructions of this manual.
Set the air output according to the
instructions of this manual.
Replace it.
9
GB
SOLUTION
Table des Matières
loading

Ce manuel est également adapté pour:

Mack 5sp515 t3515 t580990208099040

Table des Matières