Precaution Of Laying Wires; Procedures For Electrical Wiring Work - Gree Super Free Match Série Manuel D'utilisateur

Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

Super Free Match Series

7.5 Precaution of Laying Wires

1)
Use a wire stripper to strip off a length of the insulation layer at the end of the wires;
2)
Loosen the screws on the terminal block of the air conditioner;
3)
Press the ends of the cable tightly onto the round terminals corresponding to the size of the
screws.
4)
Pass the screw through the round terminals and fix it onto the terminal block.

7.6 Procedures for Electrical Wiring Work

1)
Knock the holes in the plate of the chosen direction with a hammer.
2)
Place the rubber ring on the knockout hole.
3)
Let the power cable and transmission line go through the knockout hole.
4)
Connect the power cable of the outdoor unit to the L1, L2, L3, N terminals and as well as the
ground screw.
5)
Connect the power cable of the BU modules to the L, N terminals and as well as the ground
screw.
6)
Connect the transmission line of the outdoor unit to the N(1), 2 terminals.
7)
Fix the power cable and transmission line firmly by cable fixing clip. In order to protect the
power cable and transmission line from damage by the pipes or others,
2cm away is essential.
8)
Screw the coping plate, front side plate, right connection board, front connection board back.
9)
Cover the through-holes with sealing materials to prevent the water, dust or small animals going
into the outdoor unit.
-------------------------------------------------------------------------------------------------------------------------
Caution!
The transmission line and the power cable must be separated with an interval of at least 2cm;
otherwise it may be
 In order to protect the power cable and transmission line from damaging by the hole, the rubber
ring must be placed on the hole. Otherwise, it
 The power cable and transmission line must be more than one meter away from televisions or
radios which can emit electromagnetic waves to prevent image interference or noise. Otherwise,
the unit maybe cannot work.
 Confirm the each cable connected to the terminal screw is exactly and securely after finishing
the electric work.
 Fix each ground wire separately with the ground screw.
 If the connecting wire is connected to the terminal incorrectly, the unit will not work normally.
-------------------------------------------------------------------------------------------------------------------------
Fig. 21
result in communication problem.
may cause electrical shock or fire etc.
20
an interval of at least

Publicité

Chapitres

Table des Matières
loading

Ce manuel est également adapté pour:

Super free match gwhd48snm3doSuper free match gwhd56snm3do

Table des Matières