Statement Of Conformity - Textron GREENLEE CM-1360 Manuel D'instructions

Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

1.800.544.2843
Specifications
Display: LCD, 3-5/6 digits 6000 counts
Polarity: Automatic
Update Rate: 5 per second nominal
Operating Conditions:
-10 °C to 10 °C (14 °F to 50 °F), relative humidity non-condensing
11 °C to 30 °C (51.8 °F to 86 °F), relative humidity ≤ 90%
30 °C to 40 °C (86 °F to 104 °F), relative humidity ≤ 75%
40 °C to 50 °C (104 °F to 122 °F), relative humidity ≤ 45%
Pollution degree: 2
Indoor use only
Altitude:
Operating: Below 2000 m (6500 ft)
Storage: 3000 m (9843 ft)
Storage Temperature: -20 °C to 60 °C, relative humidity < 80%, with batteries removed
Temperature Coefficient: Nominal 0.10 x (Accuracy) per °C below 18 °C from -10 °C to 18 °C
(14 °F to 64.4 °F) and above 28 °C from 28 °C to 50 °C (82.4 °F to 122 °F) or otherwise specified
Sensing: True RMS
E.M.C.:
Meets EN61326-1:2006 (EN55022, EN61000-3-2, EN61000-3-3, EN61000-4-2, EN61000-4-3,
EN61000-4-4, EN61000-4-5, EN61000-4-6, EN61000-4-8, EN61000-4-11)
In an RF field of 1 V/m, resistance modes all models and DC μA (CMH-1000 and CMI-1000):
Total Accuracy = Specified Accuracy + 80 digits
In an RF field of 1 V/m at frequencies 200 MHz ~ 300 MHz, DCA, DC+AC A and ACA mode:
Total Accuracy = Specified Accuracy + 60 digits
In an RF field of 3V/m, all other modes and models not specified above:
Total Accuracy = Specified Accuracy + 20 digits
Safety: Double insulation per UL/IEC/EN61010-1 Ed. 3, IEC/EN61010-2-033 Ed. 1, CAN/CSA C22.2 No.
61010-1 Ed. 3, IEC/EN61010-2-032 Ed. 2 & IEC/EN61010-031 Ed. 1.1 to CAT III 600V and CAT IV 300V
AC and DC
Overload Protections:
Jaws:
Current and Frequency Function: 1000 A DC/AC RMS at ≤ 400 Hz
Terminals:
Voltage and Phase Rotation Function: 1100 V DC/AC RMS
All Other Modes and Functions: 1000 V DC/AC RMS
Transient Protection: 8.0 kV (1.2/50 μs surge)
Power Supply: Two 1.5 V AA batteries (IEC LR06)
Low Battery:
Capacitance and Frequency Functions: Approximately 2.85 V
All other Functions: Approximately 2.5 V
Current Consumption:
CM-1560 and CMI-1000: Typically 13 mA
CM-1360 and CMH-1000: Typically 4.3 mA
APO Timing: Idle for 32 minutes
APO Consumption: 5 μA typical
Dimensions: 258 mm x 94 mm x 44 mm (10.1" x 3.7" x 1.7")
Jaw Opening and Conductor Diameter: 51 mm max (2.0")

Statement of Conformity

Greenlee Textron Inc. is certified in accordance with ISO 9001 (2000) for our Quality Management
Systems.
The instrument enclosed has been checked and/or calibrated using equipment that is traceable to the
National Institute for Standards and Technology (NIST).
16
www.calcert.com
15
10
20
5
25
0
30
sales@calcert.com

Publicité

Table des Matières
loading

Table des Matières