Hydraulic Connection - Gotec RAPIDO Notice D'utilisation

Table des Matières

Publicité

Les langues disponibles
  • FR

Les langues disponibles

Alarm common
Alarm NC
Earth
Alarm NO
2.2 Electrical connection of alarm :
Neutral
NO/NC contacts are available with 8A switching resistive
Phase
current - 230 VAC/VDC max.
To use the alarm contact as "normally closed" it is necessary
to connect the alarm cable with the NC (red) and C (white).
To use the alarm contact as "normally open" it is necessary to
connect the alarm cable with NO (black) and C (white).
We advise the use of this contact to cut off refrigeration in the
event of an overflow in the detection unit.
Ensure that the electrical connections to the pump are sealed
fully using the insulating cap, which should be secured with a
cable tie.

2.3 Hydraulic connection :

On mini-split, wall mounted equipment, the detection unit is connected to the end of evacuation pipe by means of a
rubber sleeve (supplied). On other types, the rubber sleeve is connected to the drain tank outlet. The length of this
sleeve can be adjusted. The detection unit must be installed horizontally, in the location reserved inside the foam elbow
(tolerance ±7.5°). It must not be fixed on a metallic brace, to avoid dysfunction of the magnet. Install the ventilation tube
on the detection block.
The hydraulic discharge connection uses flexible piping having an inside Ø 6 mm.
The
must not be immersed or placed outside of the premises or in a damp place, or in temperature below 0°C.
RAPIDO
3. OPERATION :
Pour water into air conditioner drain tank. Check that the pump starts then stops when the water level has gone back
down. To check the operation of the alarm, continue to pour in water until the alarm triggers (cutting of the air conditioner
or generating an audible or visual alarm, etc.).
4. CLEANING :
Periodically: at the beginning of the season. Clean the detection unit. Disconnect from mains supply before opening.
Remove the lid of the elbow to reach the detection block. Remove the float, clean the detection unit and the float using a
solution of water containing 5% bleach. Replace the float in this initial position (magnet faced up), reinstall the lid. Carry
out an operating test on the pump and the alarm. When the air conditioner is installed in an area liable to cause or
favour extensive dirtying of the condensate water, maintain more frequently.
5. WARRANTY :
One (1) year as of date of delivery. This warranty concerns all parts with material defects or manufacturing faults and is
confined to the replacement or repair of the defective parts. Cost of labour and any secondary failures cannot be
considered as basis for a claim in any case.
All equipment returned must be complete and accompanied by a note indicating the observed fault.
We decline any responsibility if installation is not in conformity, if the specifications are not satisfied, if the equipment is
not maintained or if alarm is not connected.
Gotec SA, Rue des Casernes 59, CH-1950 Sion
E-Mail : info@gotec.ch
Tél. (027) 205 7 205 - Fax (027) 205 7 206
7

Publicité

Table des Matières
loading

Table des Matières