User Linearisation (±100 Mv / 500 ) - Kübler CODIX 564 Série Guide Rapide

Contrôleurs de process pour sondes de température
Table des Matières

Publicité

Les langues disponibles
  • FR

Les langues disponibles

9.3
User Linearisation
(±100 mV / 500 )
A maximum of 12 linearisation points is possible.
An input value INP must be entered for each
linearisation point (LP) - input of the sensor value
from the analogue input in physical units - as well
as the corresponding display value DISP for this
sensor value. The linearisation points (LP) may
be entered in any order. They are then sorted in
the firmware in ascending order for the
linearisation function. Linearisation based on a
negative slope is possible.
Page 12
Menu User Linearisation
Select User Linearisation
Linearisation OFF
Linearisation ON
Select number of linearisation
(control) points
Input range 3 ... 12
Select input low value
Input range depends on
measuring range [ / mV]
Select display low value for
INP.LO.
Input range
-199999 ... +999999 and DP
Select input value 1
Input range depends on
measuring range [ / mV]
Select display value for
INP.01.
Input range
-199999 ... +999999 and DP
Select input value 10
Input range depends on
measuring range [ / mV]
Select display value for
INP.10.
Input range
-199999 ... +999999 and DP
Select input high value
Input range depends on
measuring range [ / mV]
Select display high value for
INP.HI.
Input range
-199999 ... +999999 and DP
The functions LO.LIM and HI.LIM limit the
editable range.
The value for HI.LIM must always be
greater than the value for LO.LIM.

Publicité

Table des Matières
loading

Ce manuel est également adapté pour:

Codix 6.56.1.0 série

Table des Matières