Address Assignment in the F-CPU
Contrary to the information in the manual ET 200eco Distributed I/O Station, Fail-Safe I/O Module, section 4.2,
the fail safe distributed I/O station assigns the following address range in the F-CPU:
• For S7 F/FH systems: in the process image range
UL/CSA Approval
Contrary to the information in the manual ET 200eco Distributed I/O Station, Fail-Safe I/O Module, section
7.2:
• The Fail-Safe I/O Module ET 200eco does not fulfill the norm:
94/9/EC "Equipment and Protective Systems Intended for Use in Potentially Explosive Atmospheres"
(Explosion Protection Guideline).
• The Fail-Safe I/O Module ET 200eco only has cULus approval. Approvals for UL, CSA and cULus
Haz.LOC. are not available.
Parameter "Behavior after Channel Faults"
The Fail-Safe I/O Module ET 200eco setting "Behavior after Channel Faults" is configurable.
This parameter is used to specify whether the entire F-module is passivated or just the faulty channel(s) in
the event of channel faults.
The setting of this parameter is only relevant if you operate the F-module with S7 Distributed Safety V5.4 or
higher.
Section 8.2.4 Application 3: Safety Mode AK6/SIL3/Category 4
There is a mistake on pages 8-22 and 8-24 in the manual ET 200eco Distributed I/O Station, Fail-Safe I/O
Module, section 8.2.4 Application 3: Safety Mode AK6/SIL3/Category 4.
The correct translation for the last sentence in the paragraph Assignable Parameters for Application 3.1
and Assignable Parameters for Application 3.2 should be: Activate the parameter "short-circuit test."
Product Information
A5E00470176-02
3