Installation information

Always install valve in flow direction; see flow
indicating arrow on body.
To avoid unnecessarily great resistance due to indi-
vidual components, no check valves causing a high
pressure loss should, if possible, be installed.
Installation of KEMPER MULTI-FIX-PLUS Manual
Double-Regulating Valves, Figure 150 is recom-
mended in those sections of piping with the
greatest and next greatest pressure loss in order to
realise a high volume flow in such pump-remote
sections.
Warning! Technical information!
At the combination of KEMPER
MULTI-THERM Automatic Double-
Regulating Valves with central drinking
water heating system attention
2
Adjustment of set-point temperature
Remove protective cover.
Located beneath the protective cover, on the ba-
lancing head, is the adjusting cap with a tempera-
ture scale from 50 °C – 65 °C.
Loosen lateral locking screw M5 using a hex key
(size: 2.5) and select the set-point temperature by
turning the cap to coincide with the marker arrow
on the circumference of the upper section.
should be paid to the fact that the
drinking water warming up is carried
out within the operating temperature
range of balancing valves. If this is not
the case, a faulty hydraulic balance in
the drinking water warm system can
occur.
Note! The Multi-Therm Double-
Regulating Valve is factory set to 58 °C.
When installing the valve outside
Germany, an adjustment of the valve
preset must be carried out by the
customer in accordance with the PWH
/ PWH-C temperatures required in the
EU member state in question and in
accordance with the calculation results
from the national calculation standard.
Note! Do not turn beyond limit stops.
Tighten locking screw and replace
protective cover. The cover can be
secured in place by lead-sealing. The
set-point temperature is the temperature
at which the balancing valve should
attain the kvmin value.
Factory pre-setting: 58 °C
Flow diagrams
© www.kemper-olpe.de – 02.2022 / K410014100002-00 – 9 /32
Annex