Faults
If the integrated cut-off unit trips (e.g. due to age
on account of multiple, very high overvoltages),
the visual display (Figure
(grey) to red. In this case, remove the arrester
and insert a new arrester (available separately,
V20: item no. 5095 364, C20: item no. 5095 600).
In the case of devices with multiple arresters, it
must be assumed that the other arresters of this
device have experienced the same load. We rec-
ommend that you check them and, if necessary,
also replace them. Dispose of replaced arrest-
ers.
Maintenance
We recommend carrying out a visual check of
the visual display every 2-4 years or after light-
ning strikes.
Disposal
– Packaging as household waste
– Protection device/arrester as electronic waste.
Comply with the local waste disposal regulations.
OBO Bettermann GmbH & Co. KG
) switches from green

Technical data

V20 ... 440
IEC / DIN EN
61643-11
U
440 V AC
C
U
400 V AC
N
U
≤ 2000 V
P
1300 V
1 kA
8/20
U
@
res
1500 V
5 kA
8/20
I
T1
imp
I
20 kA
T2
n
I
40 kA
max
I
SCCR
I
-
fi
IP code
Number of
Ports
System
TN-, TT
Protection
L – PEN
path
L – N
Protection
L – PE
path
N – PE
x
x ≥ 1,5 mm (0.06 in)
F1 >160 A gL / gG
F1
+
F2
F2 ≤ 160 A gL / gG
F1 ≤ 160 A
F2
2
F1
gL / gG
1.5 – 35 mm
1.5 – 35 mm
1.5 – 35 mm
Accessories
a
a ≤ 15.5 mm (0.6 in)
3 x 16 mm
5012 010
V20-...-440
C20
Class II / Type 2
255 V AC
230 V AC ± 10 %
≤ 1300 V
12 kA
40 kA
60 kA
50 kA
eff
100 A
IP 20 (built-in)
One-Port-SPD
TN-, TT (NPE)
-40 – +80 °C
-40 – +176 °F
5 – 95 %
N – PE
– (NPE)
– (NPE)
(AWG 16 – 2)
2
(AWG 16 – 2)
2
(AWG 16 – 2)
2
(3 x AWG 6)
2