Paramètres Programmables - IME DG2 Série Mode D'emploi

Table des Matières

Publicité

LE11073 _01 05 - 2018
DG.A2
• Input 10A ac
10 Press
PG
to enter programming menu
20 Press
SET
until
10
range is displayed
31 Press
PG
See Programming ALARMS (40)
DG.A2
• Input 20A ac
10 Press
PG
to enter programming menu
20 Press
SET
until
20
range is displayed
31 Press
PG
See Programming ALARMS (40)
DG.G2
• Input 500V ac - TA/5 or /1A ac
10 Press
PG
the display shows - U -.
21 a
If you want to use the meter for alternating voltage measurements,
press once again
PG
(see item 40)
b
If you want to use the meter for alternating current measurements,
press SET; until desired range is displayed
31 Press
PG
See Programming ALARMS (40)
DG.S2
• Input 10...100Hz (100...500V)
This version doesn't need any range programming ; therefore you directly go
to the ALARMS programming (40).
Paramètres programmables
• ALARMES
L'appareil est pourvu de 2 alarmes complètement indépendantes et program-
mables. Pour chaque alarme il est possible de sélectionner :
- type de alarme (tP.)
maximum (Hi)
minimum (Lo)
- Seuil (St.)
- Etat des relais (rL .)
normalement désexcité (n.d.)
normalement excité (n.E)
- Hystérésis (HS.)
- Temporisation (dL.)
1...60s.
LE11073 _01 05 - 2018
3