Carel MChiller Mode D'emploi page 110

Régulation pour chiller / pompe à chaleur
Masquer les pouces Voir aussi pour MChiller:
Table des Matières

Publicité

FRE
7.4 Input
register
Index Size Ref.
Type Min/Max R/W UoM
0
2
HuP1
INT
2
2
HuP2
INT
4
2
H1C1
INT
6
2
H1C2
INT
8
2
H2C1
INT
10
2
H2C2
INT
12
2
dSt1
REAL
14
2
Sct1
REAL
16
2
dSt2
REAL
18
2
Sct2
REAL
20
2
dSP1
REAL
22
2
ScP1
REAL
24
2
Cnd1
REAL
26
2
EuP1
REAL
28
2
dSP2
REAL
30
2
ScP2
REAL
32
2
Cnd2
REAL
34
2
EuP2
REAL
36
2
HSP1
INT
38
1
C045
INT
40
2
HFn1
INT
42
2
HFn2
INT
46
2
SEtA
REAL
48
2
SSH1
REAL
50
1
Opn1 INT
51
2
SSH2
REAL
53
1
Opn2 INT
54
2
rUSr
REAL
56
2
dUSr
REAL
65
2
REAL
67
2
REAL
71
1
INT
90
2
rSPt
REAL
92
2
REAL
96
2
REAL
98
2
REAL
100
2
rps1
REAL
102
2
Mc1
REAL
104
2
MP1
REAL
106
2
Drt1
REAL
AlHs1_
108
1
INT
1
AlHs2_
109
1
INT
1
AlHs3_
110
1
INT
1
AlHs4_
111
1
INT
1
114
1
INT
115
1
INT
116
2
REAL
110  |  7. Tableaux supervision
Description
R
h
HuP1 - User pump 1 working hours
R
h
HuP2 - User pump 2 working hours
R
h
H1C1 - Compr.1 circ.1 working hour
R
h
H1C2 - Compr.2 circ.1 working hour
R
h
H2C1 - Compr.1 circ.2 working hour
R
h
H2C2 - Compr.2 circ.2 working hour
R
°C/°F
dSt1 - Discharge temp. probe of circ.1
R
°C/°F
Sct1 - Suction temp. of circ.1
R
°C/°F
dSt2- Discharge temp. probe of circ.2
R
°C/°F
Sct2 - Suction temp. of circ.2
R
bar/psi dSP1 - Discharge press. probe of circ.1
R
bar/psi ScP1 - Suction press. of circ.1
R
°C/°F
Cnd1 - Cond. temp. probe (or press. probe converted value) of circ.1
R
°C/°F
EuP1 - Evap. temp. probe (or press. probe converted value) of circ.1
R
bar/psi dSP2 - Discharge press. probe of circ.2
R
bar/psi ScP2 - Suction press. of circ.2
R
°C/°F
Cnd2 - Cond. temp. probe (or press. probe converted value) of circ.2
R
°C/°F
EuP2 - Evap. temp. probe (or press. probe converted value) of circ.2
R
h
HSP1 - Source pump 1 working hours
R
C045 - Refrigerant type (3=R407C, 4=R410a, 6=R290, 10=R744, 22=R32)
R
h
HFn1 - Source fan 1 circ.1 working hour
R
h
HFn2 - Source fan 1 circ.2 working hour
R
°C/°F
SEtA - Actual setpoint used by thermoregulation
R
K/R
SSH1 - Suction Superheat of circ.1
R
%
Opn1 - EEV position of circ.1
R
K/R
SSH2 - Suction Superheat of circ.2
R
%
Opn2 - EEV position of circ.2
R
°C/°F
rUSr - Return water temp. from user
R
°C/°F
dUSr - Delivery water temperature to user
R
%
Fan1Req - Inverter request source fan circ.1
R
%
Fan2Req - Inverter request source fan circ.2
UnitStatus - Unit status (0=OFF by remote DI, 1=OFF by keyboard, 2=OFF by scheduler, 3=OFF by BMS,
R
4=OFF by changeover mode Ch/HP, 5=OFF by alarm, 6=Unit in defrosting, 7=Unit ON, 8=Manual
mode)
R
°C/°F
rSPt - Remote set point
R
%
PwrReq - Power request
R
°C/°F
SrcSetP_Circ1 - Source fan circ.1 set point
R
°C/°F
SrcSetP_Circ2 - Source fan circ.2 set point
R
rps
PSD circuit 1:Actual rotor speed coming from inverter
R
A
PSD circuit 1: Current motor current [A]
R
kW
PSD circuit 1: Current motor consumption [kW]
R
°C/°F
PSD circuit 1: Current drive temperature[°C]
R
PSD circuit 1: the last alarm log
R
PSD circuit 1:the last-but-1st alarm log
R
PSD circuit 1:the last-but-2nd alarm log
R
PSD circuit 1:the last-but-3rd alarm log
R
MotTyp - BLDC circ.1 Carel Database ID
R
Envelope zone circ.1
R
°C/°F
EnvPnt_X1 - Envelope point
µChiller +0300053FR rel. 1.3 – 30.10.2019