Carel MChiller Mode D'emploi page 109

Régulation pour chiller / pompe à chaleur
Masquer les pouces Voir aussi pour MChiller:
Table des Matières

Publicité

Index Size Ref. Type Min/Max
294
1
Hc09 INT
0..5
295
1
Hc10 INT
0..5
296
1
Hc11 INT
0..5
307
2
SEtC REAL U006..U007 R/W °C/°F
309
2
SEtH REAL U008..U009 R/W °C/°F
324
2
C017 REAL 0..999.9
326
2
C018 REAL -99.9..99.9
328
1
E047 INT
0..2
-
335
2
P000 REAL
999.9..999.9
-
337
2
P001 REAL
999.9..999.9
339
1
P002 INT
0..999
340
1
P003 INT
0..999
341
1
P004 INT
0..999
342
2
P005 REAL 0..999.9
344
2
P006 REAL 0..100
346
2
P007 REAL 0..999.9
348
1
P008 INT
0..999
349
1
P009 INT
0..999
350
2
P010 REAL 0..999.9
352
1
P011 INT
0..999
353
1
P012 INT
0..999
354
1
P013 INT
0..999
355
1
P014 INT
0..999
356
1
P015 INT
0..999
357
1
P019 INT
0..101
358
1
P020 INT
0..101
359
2
P021 REAL
361
1
P022 INT
362
1
P023 INT
363
2
P024 REAL
365
2
P025 REAL
367
2
P026 REAL
369
2
P027 REAL 0..100
371
2
P028 REAL 20..100
373
2
P029 REAL 20..100
375
2
P030 REAL
377
2
P031 REAL
379
1
P032 INT
380
1
P033 INT
382
2
S051 REAL 0..999.9
384
2
S052 REAL 0..999.9
703
1
INT
704
1
INT
709
1
U079 INT
1..15
710
1
U080 INT
3..99
732
2
S070 REAL -99.9..99.9
734
2
S071 REAL 99.9..99.9
736
2
S069 REAL 0..99.9
µChiller +0300053FR rel. 1.3 – 30.10.2019
R/W UoM
Description
4=2nd SetPoint, 5=Remote alarm , 6=User pump 1 overload)
Hc09 - Digital input 4 config. of Slave board (0=Not used, 1=Compr.2 circ.2 overload, 2=Remote
R/W
ON/OFF, 3=Cool/Heat, 4=2nd SetPoint, 5=User pump 1 overload)
Hc10 - Digital input 5 config. of Slave board (0=Not used, 1=Compr.2 circ.2 overload, 2=Remote
R/W
ON/OFF, 3=Cool/Heat, 4=2nd SetPoint, 5=User pump 1 overload)
Hc11 - Digital input 6 config. of Slave board (0=Not used, 1=Compr.2 circ.2 overload, 2=Remote
R/W
ON/OFF, 3=Cool/Heat 4=2nd SetPoint, 5=User pump 1 overload)
SEtC - Cool setpoint
SEtH - Heat setpoint
R/W °C/°F
C017 - Threshold of max high pressure (HP)
R/W bar/psi C018 - Threshold of min low pressure (LP)
R/W
E047 - Type of ExV driver (0= Disabled, 1= EVD embedded, 2=EVD EVO)
R/W °C/°F
P000 - Evaporating min temp. custom envelop limit
R/W °C/°F
P001 - Condensing max temp. custom envelop limit
R/W s
P002 - Prevent min duration
R/W s
P003 - Out of envelop alarm delay time
R/W s
P004 - Low pressure difference alarm delay
R/W rps
P005 - Circuit destabilization min BLDC speed threshold
R/W %
P006 - Oil recovery min request for activation
R/W rps
P007 - Oil recovery min compr. speed for activation
R/W min
P008 - Oil recovery time before activation in which the compr. can run at min speed
R/W min
P009 - Oil recovery duration in which the compr. speed is forced
R/W rps
P010 - Oil recovery compr. speed in which the compr. is forced
R/W s
P011- Oil equalization startup time of solenoid valve on compr. starts
R/W s
P012 - Oil equalization solenoid valve open time
R/W min
P013 - Oil equalization solenoid valve min off time
R/W min
P014 - Oil equalization solenoid valve max off time
R/W min
P015 - Oil equalization max time for the management
R/W %
P019 - Compressor 1 circuit 1 manual mode (0=AUTO, 1=0%, ... 101=100%)
R/W %
P020 - Compressor 1 circuit 2 manual mode (0=AUTO, 1=0%, ... 101=100%)
R/W kPa
P021 - Max permitted Delta P to start up
R/W s
P022 - Max time of EVD propening to equalize pressure
R/W %
P023 - Preopening of EVD in case of prestart to equalize pressure
R/W rps
P024 - Start up speed
R/W rps
P025 - Max speed custom (rps)
R/W rps
P026 - Min speed custom (rps)
R/W %
P027 - BLDC speed request threshold % to call on it
R/W %
P028 - BLDC speed threshold to call on fixed speed compressor
R/W %
P029 - BLDC speed threshold to switch off fixed speed compressor
R/W
P030 - Skip frequency: set 1 [010]
R/W
P031 - Skip frequency: band 1 [011]
R/W
P032 - Enable motor overtemperature alarm (PTC) (0=OFF, 1=ON) [027]
R/W
P033 - Motor overtemperature alarm delay [028]
R/W rps
S051 - BLDC defrost speed
R/W rps
S052 - BLDC cycle reverse speed in defrost
R/W
MotTyp - BLDC Carel Database ID
R/W
Poles - Number of motor poles
R/W min
U079 - Burst funct. time of user pump on
R/W min
U080 - Burst funct. time of user pump off
R/W K/R
S070 - Cond.1 antifreeze temp. probe offset (S3)
R/W K/R
S071 - Cond.2 antifreeze temp. probe offset (S3 exp.)
R/W °C/°F
S069 - Temperature set point of Fan-Defrost function (0=Function disabled)
7. Tableaux supervision  |  109