Carel MChiller Mode D'emploi page 103

Régulation pour chiller / pompe à chaleur
Masquer les pouces Voir aussi pour MChiller:
Table des Matières

Publicité

Index Size Ref.
Type Min/Max
40
1
S062
BOOL
41
1
S063
BOOL
42
1
S064
BOOL
44
1
S065
BOOL
46
1
S068
BOOL
47
1
UoM
BOOL
48
1
Hc02
BOOL
49
1
Hc12
BOOL
50
1
Hc13
BOOL
52
1
Ha02
BOOL
53
1
Hd03
BOOL
54
1
UnSt
BOOL
55
1
ModE BOOL
56
1
RES
BOOL
59
1
ClrH
BOOL
63
1
Hd05
BOOL
64
1
BOOL
66
1
P016
BOOL
67
1
P017
BOOL
68
1
P018
BOOL
69
1
P034
BOOL
80
1
U078
BOOL
7.2 Input status
Index
Size
Ref.
Type
Min/Max
0
1
A01
BOOL
1
1
A02
BOOL
2
1
A03
BOOL
3
1
A04
BOOL
4
1
A05
BOOL
5
1
A06
BOOL
7
1
A08
BOOL
8
1
A09
BOOL
9
1
A10
BOOL
10
1
A11
BOOL
11
1
A12
BOOL
12
1
A13
BOOL
13
1
A14
BOOL
14
1
A15
BOOL
15
1
A16
BOOL
16
1
A17
BOOL
17
1
A18
BOOL
18
1
A19
BOOL
19
1
A20
BOOL
20
1
A21
BOOL
21
1
A22
BOOL
22
1
A23
BOOL
23
1
A24
BOOL
24
1
A25
BOOL
25
1
A26
BOOL
26
1
A27
BOOL
µChiller +0300053FR rel. 1.3 – 30.10.2019
R/W UoM Description
R/W
S062 - Source pump output logic (0=N.O., 1=N.C.)
R/W
S063 - Reverse valve output logic (0=N.O., 1=N.C.)
R/W
S064 - Source flow type (0=Independent, 1=Common)
R/W
S065 - Source fan type (0=Inverter, 1=ON/OFF)
R/W
S068 - Source type (0=Air, 1=Water)
R/W
UoM - Unit of measure used for Display 2-Row and BMS, not for Applica (0=°C/bar, 1=°F/PSI)
R/W
Hc02 - Analog channel 4 enabling (0=Disabled, 1=Enabled)
R/W
Hc12 - Digital output 6 config. (0=Antifreeze, 1=Source fan / Source pump)
R/W
Hc13 - Enable buzzer (0=Disabled, 1=Enabled)
R/W
Ha02 - Sets controller internal clock (0=No set, 1=Set)
R/W
Hd03 - Enable NFC (0=Disabled, 1=Enabled)
R/W
UnSt - Unit ON/OFF command by keyboard (0=OFF 1=ON)
R/W
ModE - Cool/Heat mode by Keyboard (0=Cool, 1=Heat)
R/W
RES - Reset active alarms by BMS net (0=NO, 1=Reset)
R/W
ClrH - Delete alarms log (0=No, 1=Yes)
R/W
Hd05 - Enable unit ON/OFF command by BMS net (0=Disabled, 1=Enabled)
R/W
Unit ON/OFF command by BMS
R/W
P016 - Oil equalization solenoid valve circ.1 output logic (0=NC, 1=NO)
R/W
P017 - Enable oil equalization function (0=OFF, 1=ON)
R/W
P018 - Enable oil recovery function (0=OFF, 1=ON)
R/W
P034 - Enable cranckcase heater (0=OFF, 1=ON)
R/W
U078 - Burst function enabling (0=Disabled, 1=Enabled)
R/W
UoM
Description
R
Unit - Error in the number of retain memory writings
R
Unit - Error in retain memory writings
R
Unit - Remote alarm by digital input
R
Unit - Alarm remote set point out of range
R
Unit - Alarm user return water temperature probe broken or disconnected
R
Unit - Alarm user delivery water temperature probe broken or disconnected
R
Unit - User pump 1 overload
R
Unit - User pump 2 overload
R
Unit - Flow switch alarm, no flow present with user pump 1 active
R
Unit - Flow switch alarm, no flow present with user pump 2 active
R
Unit - User pumps group alarm
R
Unit - User 1 pump maintenance
R
Unit - User 2 pump maintenance
R
Unit - High chilled water temperature
R
Unit - Alarm source return water/air temperature probe broken or disconnected
R
Unit - Source 1 pump maintenance
R
Unit - Free-cooling anomaly
R
Circuit 1 - Alarm discharge pressure probe broken or disconnected
R
Circuit 1 - Alarm condensing temperature probe broken or disconnected
R
Circuit 1 - Alarm suction pressure probe broken or disconnected
R
Circuit 1 - Alarm evaporating temperature probe broken or disconnected
R
Circuit 1 - Alarm discharge temperature probe broken or disconnected
R
Circuit 1 - Alarm suction temperature probe broken or disconnected
R
Circuit 1 - High pressure alarm by pressure switch
R
Circuit 1 - High pressure alarm by transducer
R
Circuit 1 - Low pressure alarm by transducer
7. Tableaux supervision  |  103