Measuring range of the module
For the measuring range and its significance please refer to the follo-
wing tables:
Analogue input module 4 ... 20 mA
Range
[mA]
< 3.4
3.4...3.59
3.6...22
22.01...23
> 23
* master replaces the (transmitted value)* by the default value 7FFFh
** the accuracy is only achieved in the nominal range (4...20 mA), it is
not guaranteed in the extended nominal range.
*** only for parameter bit 2 = 1

Technical data

Technical data and further information at
www.ifm.com Select your country Data sheet direct
Units
dec.
(32768)* 32767
(3400...3599)* /
(0D48 ... 0E0F)* /
32767
3600...22000
(22001...23000)* /
32767
32767
Units
LED 1
hex.
(8000)* 7FFF
flashes
flashes
7FFF
0E10 ... 55F0
(55F1.. 59D8)* /
flashes
7FFF
7FFF
flashes
Peripheral
fault
on ***
off
below nominal
on
off
nominal range**
off
above nominal
on ***
Meaning
wire break
range
extended and
range
outside range