Maintenance (Continued)
Assembly after maintenance
1. Bearing in mind the following points, assemble the parts following the
sequence for their removal in reverse.
Align the air filter with the grooves on the Lossnay and holder and
push it in.
When installing the air filters, take care not to damage the exposed
surfaces of the Lossnay cores.
Names of the parts
Models LGH-50 to 100 RX
1.Maintenance cover
2.Control box
5.Lossnay core
6.Air exhaust fan
Specifications
Line
Voltage
Model
frequency
(V)
name
(Hz)
LGH-
1-Phase
60
50RX
-CAN
3
208 - 230
LGH-
1-Phase
60
100RX
-CAN
3
208 - 230
LGH-
1-Phase
60
200RX
-CAN
3
208 - 230
After-sales servicing
Consult with your dealer about the after-sales services provided for this
Lossnay product.
4
3
3.Lossnay core holder
4. Air supply fan
7.Air filter
8.Damper plate
Power
Current
Fan speed
consumption
(A)
(W)
Extra High
1.23-1.25
253-278
High
1.0-1.04
207-237
Low
0.56-0.60
116-139
Extra High
2.9-2.9
596-654
High
2.5-2.5
526-578
Low
1.6-1.7
336-390
Extra High
5.7-5.7
1200-1290
High
5.1-5.1
1058-1161
Low
3.3-3.4
682-786
2. Press the filter button on the remote controller (PZ-41SLB-E) two
times in succession.
(This clears the Lossnay 's operating time cumulative data.)
Relevant button
FILTER
(Press twice)
Model LGH-200 RX
1. Maintenance cover
2.Control box
5. Lossnay core
Air volume
Static pressure
3
(m /h)
(L/S)
(mmH
O)
(Pa)
2
500
139
11.2-20.9
110-205
420
117
7.1-14.8
70-145
260
72
3.1-7.1
30-70
1000
278
14.3-20.9
140-205
900
250
11.2-17.3
110-170
650-700
181-194
6.1-10.2
60-100
2000
556
11.7-20.4
115-200
1800
500
9.2-16.3
90-160
1250-1350
347-375
4.6-9.2
45-90
If you hear strange sounds, if no air is blown out or if some other
trouble occurs, switch off the power and contact your dealer.
Consult with your dealer concerning the cost of inspection or
repair work.
Relevant display items
FILTER
3
3. Lossnay core holder
7. Air filter
6. Air exhaust fan
Excharge efficiency (%)
Enthalpy
Temperature
the unit
Heating Cooling
73
66
47
75
69
49
81
75
57
74
68
48
76
69
50
79-79
73-72
56-54
73
68
48
75
69
50
79-78
74-73
56-55
4. Air supply fan
8. Damper plate
Noise (dB(A))
Weight
Below
Air
(kg)
outlets
33-36
41-44
33
30-32
36-40
24-25
29-31
37-39
45-47
72
35-37
42-45
28-30
34-37
39-41
50-52
179
37-39
47-49
30-32
39-41

Publicité

Table des Matières
loading

Ce manuel est également adapté pour:

Lossnay lgh-100rx3-canLossnay lgh-200rx3-can

Table des Matières