Gree GMV-80WL A-T Manuel De L'utilisateur page 15

Système drv multiple de l'onduleur dc
Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

Total length (actual length) of fitting pipe
Length of farthest fitting pipe (m)
From the 1
Height difference between ODU
and IDU
Height difference between IDUs
4.2.3 Dimension of Pipe (Main Pipe) from ODU to the 1st Indoor Branch
Dimension of pipe from ODU to the 1st indoor branch will be determined by the dimension
of outdoor connection pipe.
Dimension of outdoor connection pipe
Basic module
GMV-80WL/A-T
GMV-100WL/A-T
GMV-121WL/A-T
GMV-80WL/C-T
GMV-100WL/C-T
GMV-121WL/C-T
GMV-120WL/C-T
GMV-120WL/C-X
GMV-140WL/C-T
GMV-140WL/C-X
GMV-160WL/C-T
GMV-160WL/C-X
Copyright 2018. This translation is property of GREE PRODUCTS SL. All rights reserved. Total or partial reproduction without its express authorization is prohibited.
Actual length
Equivalent length
st
branch to the farthest indoor pipe
ODU at upper side
ODU at lower side
DC Inverter Multi VRF System User Manual
Allowable
value
300m
120m
150m
40m
50m
40m
15m
Fig.8
Pipe dimension
Gas pipe (mm)
Φ 15.9
Φ 15.9
Φ 15.9
Φ 15.9
Φ 15.9
Φ 15.9
Φ 15.9
Φ 15.9
Φ 19.05
12
Fitting pipe
L1+L2+L3+a+b+c+d
L1+L2+L3+d
L2+L3+d
——
——
——
Liquid pipe(mm)
Φ 9.52
Φ 9.52
Φ 9.52
Φ 9.52
Φ 9.52
Φ 9.52
Φ 9.52
Φ 9.52
Φ 9.52

Publicité

Chapitres

Table des Matières
loading

Table des Matières