VII.2- Displaying and regulating the set point temperature:
NB: the set point temperature must be set in the following three parameters:
SETC, SETH, CF29.
Nota : IIt is only possible to change the parameter CF29 (set point) when the machine is stopped (see
paragraph VII-3).
Press the SET key to display the pool water temperature set point, this temperature set point remains on the
screen for 5 seconds (" SetC " or " SetH " appears underneath).
The set point temperature factory setting is 28°C.
To modify this setting, keep the SET key held down for 3 seconds until the displayed set point value begins to
blink.
- SetC appears: keep the s key held down to increase this value, or the t key to decrease the value.
Once the required value is achieved, press SET again to validate (the display blinks for 2s)
- SetH is displayed: keep the s key pressed down to increase this value , or the t key to decrease this value.
Once the desired value is displayed, press SET again to validate the selection (this value blinks for 2s).
- Press " SET+ snow flake ", ALL appears, use the s key until CF is displayed. Press SET again, CF29
appears, press SET to modify this value using the s t keys. Once the desired value is displayed, press SET
again to validate the selection. PAS and PR2 are displayed on the screen, press M. CF appears, press "SET +
sun", the pool water temperature is displayed on the screen.
VII.3- Starting and stopping the heat pump:
Start:
If the pool temperature is higher than the set point, press the snow flake.
If the pool temperature is lower than the set point, press the sun.
Keep the "sun" or "snow flake" keys held down for seconds, the LED under the "sun" or the "snow flake" blinks.
The heating function is activated: If the pool water requires heating, the compressor and fan start, and the
compressor and fan icons on the control panel and the remote installed control unit light up.
If the flow rate through the heat exchanger is insufficient, the message "Flow!" is displayed on the right
hand side of the control panel screen (and on the remote installed control unit screen). In this case, if filtration is
already running, open the valves on the by-pass loop until an adequate flow rate is established.
Stop:
Heating mode; To stop the machine, hold the UP key on the control panel down for 5 seconds( the "sun"
key on the remote installed control unit). "Zz" will blink and then remain lit constantly when the machine stops.
Chill mode; To stop the machine, hold the DOWN key on the control panel down for 5 seconds( the "snow
flake" key on the remote installed control unit). "Zz" will blink and then remain lit constantly when the machine
stops.
To avoid damaging the compressor, start up of the compressor is delayed if you try to restart the machine
after shutting it down (a delay of 2 minutes after pressing s). The compressor icon blinks during this delay.
The 2 minute delay will be applied every time the machine is started up.
VII.4- Other displays:
Starting from the default display, press the s or t keys to display the following successively:
o Defrosting probe temperature ("Pb3" under the value)
o Pool water temperature at the heat pump inlet
o Pool water temperature at the heat pump outlet