10
wt:hh:mm
..... Write current time (24 hr format)
wtune[i] ...... Optimize CCD read time (wtune+ to enable, wtune- to disable)
wz:xxx ........ Write time zone (see user guide for complete list of codes)
x[i] ........
Serial mode (1:half-duplex, 2:full-duplex)
y ............. Signal Strength
z[i;j] ........ Temperature [j] for analog output Zero on channel [i]
Commandes séries qui s'appliquent aux protocoles séries:
Commandes pour le protocole « Modbus over Ethernet » :
modbusid:XXX .. Set address id for Ethernet MODBUS (1 to 247, up to 255 is tolerated)
DNP 3.0 serial configuration commands:
DNP3:b,p,s .... DNP 3.0 serial configuration tool. Usage:
b (baud)
p (parity)
s (stop bits); Example:
ethmaster:XXX ..Set Ethernet DNP 3.0 master station addr (normally 65500)
ethsecond:XXX ..Set Ethernet DNP 3.0 secondary station addr (normally 1)
16bitDNP3 ......Set DNP 3.0 protocol to 16 bit mode
32bitDNP3 ......Set DNP 3.0 protocol to 32 bit mode
DNP3config .....Display current DNP 3.0 16 or 32 bit setting
master:XXXXX ...Define serial DNP 3.0 master station addr (default 65500)
second:XXXXX ...Define serial DNP 3.0 secondary station address also
understood to be 408 slave address (default 1)
IEC 60870-5 configuration commands:
60870:b,a ......60870-5-101 serial configuration tool. Usage:
b (baud)
a (addr)
eth60870id:XX ..Set address id for Ethernet IEC 60870-5-104 (1 to 255)
60870id:XXX ....Set address id for serial port IEC 60870-5-101 (1 to 255)
IEC 61850 related commands (and NTP server):
61850secur:XX ..Set Security Mode, can be ON or OFF (Ethernet IEC 61850)
61850ropass:XX .Set password for read only features (Ethernet IEC 61850)
61850lrwpass:XX Set password for limited read-write (Ethernet IEC 61850)
61850crwpass:XX Set password for complete read-write (Ethernet IEC 61850)
NTP:xxx ........Network Time Protocol service (xxx is ON or OFF)
NTPSERVERIP:xx .NTP server ip address (xx must be a valid IP address)
NTPTEST ........Try synchronizing with configured and enabled NTP server
Toutes les commandes doivent être terminées par un retour de chariot (
fichiers sont sensibles à la case (une majuscule est différente d'une lettre minuscule).
Neoptix Canada LP ©
1 hour
: 0=9600, 1=19200, 2=38400, 3=57600, 4=115200
: 0: none, 1: odd, 2: even
DNP3:2,0,2
: 0=9600, 1=19200, 2=38400, 3=57600, 4=115200
: 1 to 255 (dec); Example:
Document G1044FRr08
60870:0,27
¥
) et sont insensibles à la case. Toutefois, les noms de
94