ELECTRICAL CONNECTIONS

The three-phase power supply line must have a switch with fuses.
The regulations further require a switch on the burner's power sup-
ply line, outside the boiler room and in an easily accessed position.
For the electrical connections (line and thermostats), follow the
wiring diagram enclosed. To carry out the connection of the burner
to the power supply line proceed as follows:
1) Remove the lid by unscrewing the 4 screws (1) in figure
1,without removing the transparent door.In this way the
burner's electrical panel can be accessed.
2) Slacken le screws (2) and, after removing the cable float (3),
pass the two 7 and 4 pole plugs through the hole (see figure 2).
Connect the power supply cables (4) to the contactor, connect
E
the cable to ground (5) and close the cable holder.
3) Reposition the cable float as in figure 3. Turn the cam (6) so
N
that the float exerts sufficient pressure on the two cables, then
G
tighten the screws that fasten the cable float. Finally, connect
the two 7 and 4-pole plugs.
L
IMPORTANT: the housings for the cables for the 7 and 4-pole
I
plugs are provide respectively for cable Ø 9.5÷10 mm and
Ø 8.5÷9 mm, this to make sure the protection rating is IP 54
S
(standard IEC EN60529) for the electrical panel.
H
4)
To reclose the electrical panel lid, tighten the 4 screws (1)
with a torque of about 5 Nm to ensure the correct seal. At this
point, to be able to access the control panel (8), unfasten the tran-
sparent door (7), using slight touch pressure in the direction of the
arrows in figure 4, move it the short distance to separate it from the
lid.
5)
to properly resecurethe transparent door on the panelproceed
as indicated in 5:position the hooks at their hooking points and (9)
slide the door in the direction indicated by the arrow until it clicks.
It is now well sealed.
Important: only qualified technicians may open the burner's
electrical panel.
Figura 1
26 / 75
0006081327_200807
Figura 2
Figura 3
Figura 4