LG ESS Home 8 Manuel D'installation page 34

Masquer les pouces Voir aussi pour ESS Home 8:
Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

34
Installation
D
2
NOTE
y The N (neutral) hole in the contact carrier must be connected to the N(neutral) terminal
of the AC circuit breaker on the distribution box correctly. Otherwise the product could be
damaged seriously.
y The PE (Protective Earth) grounding connector in the contact carrier must be connected
to the 6 (Grounding) terminal of the distribution box correctly. Otherwise the product
could be damaged seriously.
E
Connect the wires to the corresponding
wire holes on the contact carriers.
Wire hole 1 ↔ Grid wire L1
Wire hole 2 ↔ Grid wire L2
Wire hole 3 ↔ Grid wire L3
Wire hole N ↔ Grid wire N
Wire hole 6 ↔ Grounding wire PE
And then fasten the screws on the
cantact carriers. (1 N.m)
Push the contact carriers into the housing
until it clicks.