9.7 - ELECTRIC HEATING SAFETY
F
• Units with electric heating are equipped with an automatic-reset and a manual-reset safety
thermostat.
GB
• The later operates in case of excessively low or non-existent air fl ow.
Possible causes:
- faulty fan motor,
I
- turbine blocked or strained,
- clogged fi lter,
- heat exchanger clogged,
E
- air inlet or outlets obstructed.
• Correct the fault then reset the safety thermostat as follows:
D
- turn off and lock out the unit's power supply,
- remove the / grille (see paragraph 9.5),
- remove the condensate tank (see removal in paragraph 9.5),
- the safety thermostats are located on a support against the exchanger's sheeting, on the turbine side,
- press the button in the center of the manual thermostat.
9.8 - FUSE
• A fuse (F1) located on the printed circuit board protects the unit's circuitry (see electrical diagram).
- Rating : 4 A - 250 V.
- Type : F - High breaking capacity.
- Size : 5 x 20.

10 - WIRING DIAGRAMS

14
SYMBOLS OF COMPONENTS
B1
Level sensor
B2
Automatic safety thermostat
B3
Manual safety thermostat
C1
Fan condenser
EV1 Control valve (cool)
EV2 Control valve (heat)
F1
Fuse
K1
Alarm relay
K2
Alarm relay
KM1 Heating relay
M1
Fan
M2
Condensate pump
PCB Printed circuit board
R1
Electric heating element
R2
Electric heating element
COLOURS OF THE WIRES
BK
Black
BN
Brown
BU
Blue
G
Grey
RD
Red
WH White
YE
Yellow
Manual safety thermostat