Safety Instruction:
The installation, operation, and maintenance
must be carried out by an electrician suitably
trained in hazardous areas with knowledge of
increased safety explosion protection IEC
60079-14.
Observe the national safety rules
and regulations during installation.
The technical data indicated on
the
LED
luminaire
observed.
Changes
of
the
modifications to the LED luminaire
are not permitted.
Repairs must only be carried out
by a qualified electrician with
hazardous area knowledge.
No user serviceable parts inside.
No field replaceable parts.
Conditions for Certification:
1.
The
unit is a factory sealed
product, do not attempt to open;
return to the manufacturer for
service or repair.
2.
The unit is to be suspended such
that no tension is applied to the
supply cable.
3.
The
integral
cable
terminated in a suitable terminal or
junction facility.
4.
This equipment includes some
external
non-metallic
including the outer protective
coating and lens. Cleaning shall
only be carried out with a damp
cloth.
5.
The external plastic guard on the
LED Luminaire with Sand Blast
Shield is to be cleaned with a
damp cloth only.
6.
FOR HLA UNITS ONLY
The maximum flameproof gap in
the flange of the power supply
enclosure is 0.1mm.
Introduction
The High Bay lights are designed for illumination of
industrial locations and use the latest in solid state
lighting technology for long life, low maintenance,
and high efficiency.
The unique optical design focuses light downward
to where it is needed, giving improved efficiency
over a conventional HID luminaire.
Conformity with Standards
This equipment conforms to the standards specified
in the Declaration of Conformity. It has been
designed,
manufactured
and
accordance with:
BS EN 9001.
ATEX
Directive
2014/34/EU:
protective systems intended for use in potentially
explosive atmospheres.
EMC Directive 2014/30/EU: For electromagnetic
compatibility.
Equipment Application
This lighting equipment is intended for use in a
Page
3
ATEX/IECEx Rated LED High Bay Luminaire
potentially explosive atmosphere in Zones 1, 21 and
2, 22 to the requirements of ATEX Directive
2014/34/EU. The product can be used inside or
outside to illuminate areas with a potentially
explosive atmosphere.
General Mounting Information
For maximum long term reliability and light output, the
light must be installed in free air. The High Bay
luminaire design incorporates an over-temperature
control circuit that reduces input power should internal
is
to
be
temperatures reach a maximum level. As a result, light
output may be temporarily reduced at higher ambient
temperatures.
design
and
Recommended mounting height: 6-12m [20-40ft]
Stirrup Mounting Information
The 'Stirrup Bracket' is fixed into place using 2 bolts
and the threaded holes on the side of the luminaire.
When secured into the desired position the 2 bolts
should be tightened to 8.0 – 10.0Nm [6 – 8ft.lbs].
For 25K (HLA) models:
M8 bolts: 19Nm
M6 bolts: 7Nm
Electrical Installation of Luminaire
Ensure
that
disconnected before connecting the luminaire.
Install the equipment in accordance with the
manufacturer's instructions as well as any other
applicable electrical codes.
is
to
be
Always transport and store the equipment in its original
packaging and keep in a dry location. When
unpacking check for any cracks or damage in the
housing, glass, and glass frame. If in doubt, do not
install.
parts,
Note: Electrical installation of the extension should
be carried out by a qualified electrician.
For connecting the coloured fitted power cable
conductors is as follows:
- Brown wire connects to Live.
- Blue wire connects to Neutral.
- Green/Yellow wire connects to Safety Ground
(Earth).
For connecting the numbered fitted power cable
conductors is as follows:
- Wire 1 connects to Live.
- Wire 2 connects to Neutral.
- Wire 3 connects to Safety Ground (Earth).
WARNING: Do not remove or tamper with the certified
cable gland. The Ex 'd' rated gland has been
supplied and installed to the luminaire in accordance
with the manufacturer's instructions. Tampering with
this cable gland may compromise the IP66 rating and
result in flame propagation into the atmosphere.
Electrical Installation of Junction Box
The cable glands used with this luminaire must be
certified to the Ex 'e' requirements. The cable used
must be suitable for the site application and/or the
site requirements.
When assembling the cable entries for the mains
tested
in
connection, always observe the manufacturer's
specifications for the glands used. Unused cable
entries must be closed and sealed by a certified
Equipment
and
blanking plug. The cable entries should be securely
tightened to ensure that the minimum protection
rating is achieved. The cable entry should be rated
to minimum of IP66 to maintain the protection level
of the luminaire.
NOTE: This fixture is supplied with one dust cap and
one certified blanking plug.
the
mains
voltage
supply
Dialight, 1501 Route 34 South, Farmingdale, NJ, USA 07727
Tel: 732 919 3119
NOTE: Do not over tighten the cable glands as the
protection rating may be compromised. Refer to
gland manufacturer's data for torque settings.
The push terminal block (WAGO 862 series)* is
suitable for multi-stranded and single core cables
up to a maximum of 4mm2, strip length 10mm. Push
down at the 'cross point', insert correct cable and
release, ensuring the cable has been securely
retained.
The screw terminal block (Weidmüller MK 6/2/E)* is
suitable for multi-stranded and single core cables
up to a maximum of 6mm2, strip length 9mm.
Unscrew retaining tab, insert wire and tighten the
screw to 1.2-2 Nm, ensuring the cable has been
securely retained.
Loop Through Electrical Connections (for push
terminal block only)
Connect incoming cable as above then connect
the outgoing cable to the associated adjoining
connection to pass to the next luminaire.
NOTE: Only one cable to be used on each terminal
is
entry point.
Any
improper
installation,
maintenance of these luminaries may result in the
invalidation of the warranty.
Taking into Operation
Prior to operating, check the luminaire for its correct
installation in compliance with these operating
instructions and other applicable regulations.
NOTE: Only certified equipment may be put into
operation.
Chemical Compatibility Guide
The chemical compatibility data referenced in this
manual
was
supplied
by
manufacturers and is intended as a general guide.
The data represents the basic material properties
and
does
not
necessarily
performance
of
the
final
manufacturing process and design variations for
each final product. Chemical compatibility is highly
dependent
on
concentration,
humidity, and other environmental conditions and
therefore the customer assumes responsibility for
evaluation of gaseous or direct contact chemical
compatibility
at
their
site
installation.
www.dialight.com/pubs/MDTFCHEMRFLX001.pdf
* All product names, logos, and brands are property
of their respective owners. All company, product
and service names used in this document are for
identification purposes only. Use of these names,
logos, and brands does not imply endorsement.
9100127269899 REV H
Fax: 732 751 5778
operation,
or
the
raw
material
represent
the
product
due
to
temperature,
prior
to
product
www.dialight.com

Publicité

loading

Ce manuel est également adapté pour:

Iecex